Vertiv
| Liebert
®
EXM
™
Battery Cabinet User Manual |
35
4.0
SPECIFICATIONS
Table 11
Physical standards and parameters
Battery Cabinet Parameters
Values
Standard Color
Black (ZP-7021)
Front Door Opening (for serviceability)
More than 180°
Degree of Protection for UPS Enclosure
IP 20 (with and without front door open)
Minimum Clearance, Top
24" (610mm)
Minimum Clearance, Back
0"
Minimum Clearance, Sides
0"
Cable Entrance
Top or Bottom
Standards & Conformities
UL 1778 5th Ed.; CSA 22.2 107.3-14
FCC Part 15, Class A; ISTA Procedure 1H; WEEE;
IBC 2012/CBC 2010
Environmental
Storage Temperature Range, °F (°C)
-13°F to 158°F (-25°C to 70°C)
74°F to 80°F (23-27°C) for optimal battery life
Operating Temperature Range, °F (°C)
32°F to 104°F (0 to 40°C)
74°F to 80°F (23-27°C) for optimal battery life
Relative Humidity
up to 95% Non-Condensing
(Operating and Non-Operating)
Maximum Altitude Above MSL, ft (m)
4920 (1500) (as per IEC 62040/3) -
1% Maximum kW derate / 100m rise between 1500-3000m
Table 12
Battery cabinet system - breaker details
UPS Rating,
kVA
Battery
Cabinet
Breaker
Fram
e
ABB Part #
Battery Cabinet Size,
mm
10-40
225A
TS3N
TS3N225TWBAS
1
320, 600, 880
XT4
XT4NU3225AFF
000
60-120
555A
T6N
T6N600TWAS2
600, 880
140-200
555A
T6N
T6N600TWAS2
Two Battery Cabinets,
600
Two Battery Cabinets,
880