Installation
User Manual 10H52226UM60 - Rev. 1 - 01/2017
45
3.4.2. Primary line power input
These should be capable of protecting the primary AC line power ahead of the UPS. It should be able
to handle the maximum input current of the UPS (Table 1 on page
38
) and to interrupt the circuit at
its maximum current level during a short circuit.
3.4.3. Bypass line power input
Bypass line power input protection devices must have the following characteristics:
1
Maximum current rated in accordance with the values in Table 1 on page
38
;
2
I
2
t
rating
lower than
the thyristor rating (see chap. 9. on page 1
02
for pre-arc
I
2
t ratings) in order
to protect it in case of output short circuit. To allow for component tolerances, the external
protection device pre-arc I
2
t rating should not exceed 80% of the thyristor I
2
t rating;
3
Pre-arc I
2
t rating higher than that of the Inverter fuse (already installed inside the UPS - see chap.
9. on page 1
02
for pre-arc I
2
t ratings) so that the Inverter fuse will blow in case of an overcurrent
caused by an internal failure. In this case the load is supplied by the Bypass - to allow for
component tolerances, the external protection device pre-arc I
2
t rating should be at least 20%
higher than that of the Inverter fuse.
3.4.4. Battery input
These should be capable of protecting the battery against short-circuits, and should take into account
the maximum current drain (during discharge at 1.8V per cell), see Table 1 on page
38
. These devices
should be installed as close as possible to the battery.
3.4.5. UPS Output line
Since load(s) can be supplied through the Uninterruptible Power System from two sources, the ratings
of the following supplies should be taken into account when designing the output line protection
system.
Supply from inverter:
see Table 1 on page
38
and chap. 9. on page 1
02
Supply from Static Bypass Switch and maintenance Static Bypass Switch:
see Table 1 on page
38
and chap. 9. on page
102
N.B.
If a single differential breaker is installed ahead of the UPS, any fault in the installation
grounding system will result in the interruption of power to both the line power input and the direct
line.
3.5. Backfeed protection
To prevent electric shock hazards caused by backfeed through the Static Bypass Switch, an external
disconnector must be installed in conformance with Product Standard IEC/EN 62040-1+A1:2013. The
UPS generates a logic command at X29 (see Fig.
40
) to ensure that the disconnector operates
correctly.
N.B.
In case of single-line feeder, the disconnector must be installed ahead of the UPS primary and
bypass inputs. When this disconnector is activated, the UPS switches to Battery Mode.
N.B.
The PE and N terminals must be connected in accordance with the requirements of the local
line power distribution system (TN-C, TN-S, TN-C-S, TT etc.). For instance, in
TN-C installations the PEN conductor from the supply transformer must be connected to the UPS PE
and N terminals. See para. 3.6 on page
46
and Fig.
50
on page
91
.
Summary of Contents for Liebert EXL
Page 1: ...Liebert EXL User Manual...
Page 2: ...Liebert EXL UNINTERRUPTIBLE POWER SUPPLY USER MANUAL 10H52226UM60 rev 1...
Page 7: ...Liebert EXL S1 6 User Manual 10H52226UM60 Rev 1 01 2017...
Page 36: ...Preparation For Use Liebert EXL S1 35 User Manual 10H52226UM60 Rev 1 01 2017 BLANK PAGE...
Page 74: ...CONNECTIVITY PANELS Liebert EXL S1 73 User Manual 10H52226UM60 Rev 1 01 2017 BLANK PAGE...
Page 84: ...Normal and safe operation Liebert EXL S1 83 User Manual 10H52226UM60 Rev 1 01 2017 BLANK PAGE...
Page 86: ...Maintenance Liebert EXL S1 85 User Manual 10H52226UM60 Rev 1 01 2017 BLANK PAGE...
Page 94: ...PARALLEL CONFIGURATION Liebert EXL S1 93 User Manual 10H52226UM60 Rev 1 01 2017 BLANK PAGE...
Page 102: ...Options Liebert EXL S1 101 User Manual 10H52226UM60 Rev 1 01 2017 BLANK PAGE...