17. Change the parameters to match the parameters from the control board that was removed if
they were obtained from the old board in step 4. See step 18 if the parameters were unavailable.
18. If the old board parameters were unavailable, use the new HMI label included in kit to obtain
the proper settings. Parameters C03, C04, C05 and C06 must be programmed with the proper
EC fan supplier used on the unit.
19. Address the fans (refer to
20. Compare the HMI label on the unit with the latest revision.
•
If there are differences, clean and dry the surface of the old HMI label; attach the new
label on top of the old label, covering the old label with the new one.
21. Verify that the control board is reading pressure and temperature.
22. Verify that there are no communication alarms with the fans or with the cooling unit the
condenser is serving.
23. Verify proper fan operation by adjusting the cooling unit that this condenser serves so that it
calls for cooling.
8.11 Pumped-refrigerant Economizer (PRE)
Your Liebert® DP060 includes a Liebert® PRE system. Refer to the Installer/User Guide for the economizer,
SL-18920, for the maintenance and operation details.
Vertiv | Liebert® DSE060™ Installer/User Guide
60
Summary of Contents for Liebert DSE060
Page 18: ...Vertiv Liebert DSE060 Installer User Guide 18 This page intentionally left blank...
Page 22: ...Figure 4 3 Typical Center Line of Fork Pockets Vertiv Liebert DSE060 Installer User Guide 22...
Page 26: ...Vertiv Liebert DSE060 Installer User Guide 26 This page intentionally left blank...
Page 30: ...Vertiv Liebert DSE060 Installer User Guide 30 This page intentionally left blank...
Page 66: ...Vertiv Liebert DSE060 Installer User Guide 66 This page intentionally left blank...
Page 68: ...Vertiv Liebert DSE060 Installer User Guide 68 This page intentionally left blank...
Page 70: ...Vertiv Liebert DSE060 Installer User Guide 70 This page intentionally left blank...