Item
ID
Meaning
Default
Notes
P01
Enter
Preparation
Mode
0
Setting this value to ‘1’ enables preparation mode. All other ‘P—‘menu items are disabled until this
value is ‘1’. Note that control operations may be affected during preparation mode, therefore the
cooling unit should be off. Setting this value back to ‘0’ creates new default values based upon
selections in this menu. After default values are established, the board exits preparation mode and
reboots.
P02
Automatic
VSD
Configuration
1
This item should only be used to address the VSDs for the unit. The value entered indicates the
model of the VSD:
1 – EBM
2 – Ziehl-Abegg
3 – Fans Tech
All fans must be the same model to use this parameter. When
ENT
is pressed, the board will
operate and power contactors for the VSDs and assign ModBus addresses. This procedure may
take up to 5 minutes to complete.
P03
Refrigerant
Type
2
1 = R22
2 = R407C
3 = R410A
P04
Number
of Circuits
1
1 = Single Circuit
2 = Dual Circuit
P05
Liebert®
Lee Temp
Option
0
0 = No Lee Temp installed
1 = Liebert® Lee-Temp installed
P06
Condenser
1
0 = Small
Table 8.3 P-- menu items and definitions
18. Turn the power On.
19. The control board flashes
F00
on the display when it has completed its boot cycle.
20. Press the ESC button.
21. Use the UP or DOWN arrow button until
C--
displays.
22. Press the ENT button.
23. Use the UP or DOWN arrow button until
C03
displays
24. Press the ENT button.
25. Use the UP or DOWN arrow button to select one of three options:
Configuration Code
Fan #
Value
C03
Fan 1
0 = No Fan
1 = EBM Papst
2 = Ziehl-Abegg
C04
Fan 2
C05
Fan 3
C06
Fan 4
26. Press the ENT button.
27. If the new value is entered into the control board, the display flashes "
888
."
8 Maintenance
51
Summary of Contents for Liebert DSE060
Page 18: ...Vertiv Liebert DSE060 Installer User Guide 18 This page intentionally left blank...
Page 22: ...Figure 4 3 Typical Center Line of Fork Pockets Vertiv Liebert DSE060 Installer User Guide 22...
Page 26: ...Vertiv Liebert DSE060 Installer User Guide 26 This page intentionally left blank...
Page 30: ...Vertiv Liebert DSE060 Installer User Guide 30 This page intentionally left blank...
Page 66: ...Vertiv Liebert DSE060 Installer User Guide 66 This page intentionally left blank...
Page 68: ...Vertiv Liebert DSE060 Installer User Guide 68 This page intentionally left blank...
Page 70: ...Vertiv Liebert DSE060 Installer User Guide 70 This page intentionally left blank...