11. Install the new cable glands included with the new EC Fan. Torque for the cable glands is:
•
630-mm and 710-mm fans: 19.5 to 24.75 in-lb (2.2 to 2.8 Nm)
•
800-mm fans: 32.75 to 38 in-lb (3.7 to 4.3Nm)
Dispose of the old cable glands once the new glands are installed.
12. Add a compression nut to the wire—Do not tighten the nut.
13. Reconnect the wiring to the proper terminals and verify that the run jumper is in place. See
Figure 8.5 on page 48, and Figure 8.6 on the previous page, for wiring details.
•
The torque for the electrical terminals is 11.5 in-lb (1.3 Nm). Tighten the compression nut
to a torque of 22 in-lb (2.5 Nm).
14. With the PCB powered, the board display should read
F00
.
15. Press the ESC button.
16. Press the UP-arrow button once:
•
If
P- -
is displayed, perform step 17.
•
if
P- -
is not displayed, perform steps 18 through 46.
17. If
P- -
is displayed, press the ENT button to enter the P- - Menu.
The P- - Menu allows compact set-up/preparation of the condenser in the factory or in the
field. Use the functions described in Table 8.3 on the facing page, to establish a default
control configuration for the board.
NOTE: The complete list of P--, C--, and F-- parameters is located inside the lid of the electrical-box
panel.
Vertiv | Liebert® DSE060™ Installer/User Guide
50
Summary of Contents for Liebert DSE060
Page 18: ...Vertiv Liebert DSE060 Installer User Guide 18 This page intentionally left blank...
Page 22: ...Figure 4 3 Typical Center Line of Fork Pockets Vertiv Liebert DSE060 Installer User Guide 22...
Page 26: ...Vertiv Liebert DSE060 Installer User Guide 26 This page intentionally left blank...
Page 30: ...Vertiv Liebert DSE060 Installer User Guide 30 This page intentionally left blank...
Page 66: ...Vertiv Liebert DSE060 Installer User Guide 66 This page intentionally left blank...
Page 68: ...Vertiv Liebert DSE060 Installer User Guide 68 This page intentionally left blank...
Page 70: ...Vertiv Liebert DSE060 Installer User Guide 70 This page intentionally left blank...