3 PLANNING GUIDELINES
3.1 Capacity and Physical Data
Model No.
340
440
NET CAPACITY DATA kBTU/H (kW) BASED ON 45°F (7.2°C) ENTERING WATER, 10°F (5.5°C) WATER RISE
75°F DB, 61°F WB (23.9°C DB, 16.1°C WB) 45% RH
Total Capacity, kBTUH (kW)
1410 (431)
1758 (515)
Sensible Capacity, kBTUH (kW)
1184 (346)
1525 (447)
Flow Rate, GPM (l/s)
300 (18.9)
385 (24.29)
Pressure Drop, ft (kPA)
44 (130.7)
29 (87.3)
Fan Data - EC Fans - Available in Downflow Orientations
Nominal Air Volume, CFM (CMH)
45,000 (76,455)
60,000 (101,941)
Fan Motor, Maximum hp (kW), each
16.1 (12.0)
16.1 (12.0)
Standard Ext. Static Pressure, inches of water (PA)
0.3 (74.7)
0.3 (74.7)
Number of fans
3
4
Chilled Water Coil
Face Area, ft
2
(m
2
)
96 (8.91)
130 (12.08)
Number of Rows
6
6
Face Velocity, FPM (m/s)
470 (2.39)
460 (2.34)
Chilled Water Valves
Maximum design water pressure 400 PSI (2757 kPa)
Valve Actuator, Sensors and Body
Valve CV
70
130
Valve Size, in.
3.0
3.0
2-way Valve (optional) Close-off Pressure, PSI
(kPA)
100 (689)
100 (689)
Filter Section
Disposable Type - MERV8 (standard) or MERV11 (option)
Nominal Sizes, in.
20 x 24 x 4
18 x 24 x 4
20 x 24 x 4
18 x 24 x 4
Quantity of each
18
9
22
11
Connection Sizes
Chilled Water (grooved, black pipe)
4 in.
Condensate Drain
2 x 1-1/4 in.
Condensate Discharge (when supplied with pump),
O.D.
1/2-in. compression
Table 3.1 Performance data, Standard Chilled-water Unit with EC fans
3 Planning Guidelines
11
Summary of Contents for Liebert CW340
Page 1: ...Liebert CW Thermal Management System Installer User Guide 340 kW to 440 kW Capacity 60 Hz...
Page 4: ...Vertiv Liebert CW Installer User Guide 4...
Page 8: ...Vertiv Liebert CW Installer User Guide 8 This page intentionally left blank...
Page 28: ...Vertiv Liebert CW Installer User Guide 28 This page intentionally left blank...
Page 34: ...Vertiv Liebert CW Installer User Guide 34 This page intentionally left blank...
Page 36: ...Vertiv Liebert CW Installer User Guide 36 This page intentionally left blank...