CW340 & CW440
F
or
m
N
o.
: D
P
N
00
10
40
_R
E
V
4
PRIMARY CONNECTION LOCATIONS
LIEBERT CW
POINT
DESCRIPTION
X in. (mm)
Y in. (mm)
CONNECTION SIZE/OPENING
Condensate Drain
1-1/4" NPT Female
(w/ optional pump)
1/2" O.D. Cu Hose Barb
Condensate Drain
1-1/4" NPT Female
(w/ optional pump)
1/2" O.D. Cu Hose Barb
CWS1
2-way Chilled Water Supply
51-1/4 (1302)
CWS2
2-way Chilled Water Supply
16-1/2 (419)
CWR1
2-way Chilled Water Return
19-3/8 (492)
CWR2
2-way Chilled Water Return
24-1/2 (622)
HV1
Electrical Connection (High Voltage)
5-5/16 (135)
HV2
Electrical Connection (High Voltage)
10-1/16 (256)
HV3
Electrical Connection (High Voltage)
10-1/4 (260)
HV4
Electrical Connection (High Voltage)
6-1/2 (165)
LV1
Electrical Connection (Low Voltage)
11-15/16 (303)
LV2
Electrical Connection (Low Voltage)
9-11/16 (246)
LV3
Electrical Connection (Low Voltage)
7-7/16 (189)
LV4
Electrical Connection (Low Voltage)
11-1/4 (286)
LV5
Electrical Connection (Low Voltage)
9-3/8 (238)
LV6
Electrical Connection (Low Voltage)
7-3/8 (187)
LV7
Electrical Connection (Low Voltage)
5-1/2 (140)
1-1/4" (32mm) [1-5/8" (41mm) /
2-1/8" (54mm)]
9-1/2 (242)
CD1
CD2
11-9/16 (294)
4-7/16 (113)
2-5/16 (59)
11 (279)
49 (1245)
6-1/2 (166)
7-1/2 (191)
1-1/4" (32mm)
1-3/8" (35mm)
4" Groov ed Pipe
SECTION B-B
Bottom Piping Option Connection Locations
SECTION A-A
Top Piping Option Connection Locations
Notes:
1 All views shown in standard configuration. CW340 & CW440 can be ordered with piping and
electrical connection locations located on left end of unit with fan sections adjusted as required.
2. If unit is ordered with Piping & Electrical Connection locations on the left side, then the callouts &
dimensions shown in this drawing will be reversed.
3. All "X" & "Y" dimensions are from front right corner of unit as shown. If unit is ordered with Piping &
Electrical Connections on left side, then dimensions are from front left corner.
4. Knockout diameters are concentric (see Detail A & B).
5. Field pitch Condensate Drain line a minimum of 1/8" (3.2mm) per 12" (305mm). All units with a
gravity drain require an external condensate trap. Select appropriate drain system materials.
The drain line must comply with all local codes.
SECTION C-C
A
A
B
B
A
DETAIL A
B
DETAIL B
HV1
HV2
LV1
LV2
LV3
CWS1
CWR1
HV3
HV4
LV4
LV5
LV6
LV7
CWS2
CWR2
CD1
CD2
X
Y
0
X
Y
0
4
C
C
5
5
Summary of Contents for Liebert CW340
Page 1: ...Liebert CW Thermal Management System Installer User Guide 340 kW to 440 kW Capacity 60 Hz...
Page 4: ...Vertiv Liebert CW Installer User Guide 4...
Page 8: ...Vertiv Liebert CW Installer User Guide 8 This page intentionally left blank...
Page 28: ...Vertiv Liebert CW Installer User Guide 28 This page intentionally left blank...
Page 34: ...Vertiv Liebert CW Installer User Guide 34 This page intentionally left blank...
Page 36: ...Vertiv Liebert CW Installer User Guide 36 This page intentionally left blank...