REV : 1
REV DATE : 2/17
DPN003636
Page :2 /3
ANCHORAGE FOR CW440D
F
or
m
N
o.
: D
P
N
00
10
40
_R
E
V
4
SEISMIC DATA
LIEBERT CW
MIN. PAD
THICKNESS
MIN. EMBEDMENT
MIN. HOLE
DEPTH
ANSI B18.22.1-1965(R2003)
TYPE A, SERIES W PLAIN
WASHER REQUIRED AT
EACH ANCHOR LOCATION
Lbs
kg
Lbs
kg
Lbs
kg
Lbs
kg
CW440
1/2"
6500
2948
3616
1640
1910
866
991
450
Sds=1.70, Rp=6, ap=2.5, Ip=1.5
Model No.
Operating mass*
Maximum
Compresssive
Reaction
Maximum Load per Anchor
Tension
Shear
Anchor
Size
Floor Anchoring Dimensions
Front of Unit
A
A
SECTION A-A
O
3/4"
21mm
Anchor Holes
Typ. (6) Plcs
62"
1575mm
178"
4521mm
1"
25mm
Typ.
1"
25mm
Typ.
1 7/8"
48mm
Typ.
87 1/8"
2213mm
87 1/8"
2213mm
Notes:
1. Anchor Bolt sized per Hilti Kwik Bolt TZ Carbon and Stainless in Concrete, ICC ESR-1917.
Alternates are subject to review by Vertiv or Engineer of Record.
2. Specified by Engineer of Record.
3. Operating mass includes the operating refrigerant, water volume, floor stand and plenum.
2
2
2
3
EC Fans Removed
For Clarity
Summary of Contents for Liebert CW340
Page 1: ...Liebert CW Thermal Management System Installer User Guide 340 kW to 440 kW Capacity 60 Hz...
Page 4: ...Vertiv Liebert CW Installer User Guide 4...
Page 8: ...Vertiv Liebert CW Installer User Guide 8 This page intentionally left blank...
Page 28: ...Vertiv Liebert CW Installer User Guide 28 This page intentionally left blank...
Page 34: ...Vertiv Liebert CW Installer User Guide 34 This page intentionally left blank...
Page 36: ...Vertiv Liebert CW Installer User Guide 36 This page intentionally left blank...