REV : 0
REV DATE : 11/18
DPN004869
Page :1 /2
FOR ADJACENT CW305, 375, 415 UNITS
F
or
m
N
o.
: D
P
N
00
10
40
_R
E
V
4
FLOOR PLANNING DIMENSIONAL DATA
LIEBERT CW
Gasketing shown is for pictorial
purposes only to show edges of
unit that require gap sealing.
Gasketing and method to be
provided and applied by others
in the field.
Data Hall Side
1
Notes:
1. Gap is measured between frame members of adjacent units.
2. Gasketing required only on shortest section being placed adjacent to another unit.
3. View shows both Electronic Component Sections on the left. The same gasketing
instructions apply when both Electronic Component Sections are on the right, or
with one on the left and the other on the right.
2
View with both Electrical Component Sections on left
A
DETAIL A
3/4"
19mm
Minimum gap to be filled with
gasketing between each unit