8.2.4 Removing Fan Assembly
Do not attempt to remove the fan assemblies without first contacting Vertiv Technical Support at 1-800-
222-5877.
8.3 Condensate-drain and Condensate-pump System Maintenance
8.3.1 Condensate Drain
Check for and clear obstructions in tubing during routine maintenance.
8.3.2 Condensate Pump
WARNING! Risk of electric shock. Can cause injury or death. Open all local and remote electric
power-supply disconnect switches and verify that power is Off with a voltmeter before working
within the condensate pump electrical connection enclosure. The Liebert® iCOM™ does not
isolate power from the unit, even in the “Unit Off” mode. Some internal components require and
receive power even during the “Unit Off” mode of the Liebert® iCOM.
To maintain the condensate pump:
1. Disconnect power to the unit using the disconnect switch.
2. Check for and clear obstructions in gravity lines leading to the condensate pump.
3. Remove the sump, clean with a stiff nylon brush and flush with water.
4. Inspect and clear clogs in the discharge check valve and float mechanism.
5. Reassemble and check for leaks.
Vertiv | Liebert® CW™ Installer/User Guide
38
Summary of Contents for Liebert CW
Page 10: ...Vertiv Liebert CW Installer User Guide 6 This page intentionally left blank...
Page 24: ...Vertiv Liebert CW Installer User Guide 20 This page intentionally left blank...
Page 32: ...Vertiv Liebert CW Installer User Guide 28 This page intentionally left blank...
Page 34: ...Vertiv Liebert CW Installer User Guide 30 This page intentionally left blank...
Page 36: ...Vertiv Liebert CW Installer User Guide 32 This page intentionally left blank...
Page 46: ...Vertiv Liebert CW Installer User Guide 42 This page intentionally left blank...
Page 48: ...Vertiv Liebert CW Installer User Guide 44 This page intentionally left blank...