Figure 8.2 Removing and installing the air filters
Item
Description
1
Remove and install filters up and down in the columns. There are 3 filters in each column.
8.2 Fan Maintenance
8.2.1 Fan Assembly Troubleshooting
Any safety hazards stemming from the device must be re-evaluated once it is installed in the end device.
Do not make any modifications, additions or conversions to the fan assembly without the approval of
Vertiv.
WARNING! Risk of electric shock. Can cause serious injury or death. Open all local and remote
electric power supply disconnect switches and verify with a voltmeter that power is off before
working within the fan-motor electric-connection enclosures. Fan-motor controls can maintain
an electric charge for 10 minutes after power is disconnected. Wait 10 minutes after power is
verified as off before working within the electric control/connection enclosures. Use only fully-
trained and qualified HVAC technicians to perform maintenance on the fans.
Vertiv | Liebert® CW™ Installer/User Guide
36
Summary of Contents for Liebert CW
Page 10: ...Vertiv Liebert CW Installer User Guide 6 This page intentionally left blank...
Page 24: ...Vertiv Liebert CW Installer User Guide 20 This page intentionally left blank...
Page 32: ...Vertiv Liebert CW Installer User Guide 28 This page intentionally left blank...
Page 34: ...Vertiv Liebert CW Installer User Guide 30 This page intentionally left blank...
Page 36: ...Vertiv Liebert CW Installer User Guide 32 This page intentionally left blank...
Page 46: ...Vertiv Liebert CW Installer User Guide 42 This page intentionally left blank...
Page 48: ...Vertiv Liebert CW Installer User Guide 44 This page intentionally left blank...