Chapter 3 Electrical Installation 25
APM 300 Integrated UPS Single Module And Parallel System User Manual
Table 3-6
Description of output dry contact port
Position
Name
Description
J5.2
BFP_O
Bypass feedback protection relay (normally open), closed when bypass SCR is shorted
J5.3
BFP_S
Bypass feedback protection relay center
J5.4
BFP_C
Bypass feedback protection relay (normally closed), open when bypass SCR is shorted
3.2.6
Remote EPO Input Port
The UPS has the EPO function that operates by a switch on the operator control and display panel of the UPS or
by a remote contact provided by the user. The EPO key is under a hinged, plastic shield.
J10 is the remote EPO input port. The port is shown in Figure 3-9 and described in Table 3-7.
J10
EP
O
-N
O
+12V
+12V
+12V
EP
O
-N
C
Figure 3-9
Remote EPO input port
Table 3-7
Description of remote EPO input port
Position
Name
Description
J10.1
EPO_NC
EPO activated when shorted to J10.2
J10.2
+
12V
EPO activated when shorted to J10.1
J10.3
+
12V
EPO activated when opened to J10.4
J10.4
EPO_NO
EPO activated when opened to J10.3
EPO is triggered when pins 3 and 4 of J10 are shorted or pins 2 and 1 of J10 are opened.
If an external EPO facility is required, pins 1 and 2 or 3 and 4 of J10 are reserved for this function. The external
EPO facility is also connected to the normally open or normally closed remote stop switch between these two
terminals using shielded cable. If this function is not used, pins 3 and 4 of J10 must be opened or pins 1 and 2
of J10 must be shorted.
Note
1. The UPS EPO action shuts down the rectifiers, inverters and static bypass. But it does not internally disconnect the
input power supply. To disconnect all power to the UPS, open the upstream input switch when EPO is activated.
2. Pins 1 and 2 of J10 are supplied factory-shorted.
3.2.7
RS485 Port, RS232 Port And Intellislot Port
The RS485 and RS232 ports provide serial data and are intended for use by authorized commissioning and
service personnel in UPS commissioning and service.
The three Intellislot ports are used to install optional communication cards at site, including dry contact card,
Modbus card, SIC card and UF-RS485 card. For details, refer to the user manuals of these cards.
Note
Intellislot 1 port shares communication resource with the RS232 port. To avoid conflict, when the RS232 port is used for
service or commissioning, it is not recommended to use Intellislot 1 port.