30
Situation
Solution
Fault
Code
Fault Event
Icon
(flashing)
24
Battery disconnected
1.
Check if battery cable is
connected firmly.
2.
If error message remains,
please contact your
installer.
25
Inverter current is too high
for a long time
1.
Remove exessive loads.
2.
Then, restart the inverter.
26
Short circuited on inverter
output
1.
Turn off the inverter.
2.
Disconnect AC circuit
breaker first. Then,
disconnect DC circuit
breaker and then
disconect the loads.
3.
Please check if load circuit
is ok. After removing the
error, turn on the PV DC
breaker and battery
breaker.
4.
Turn on the inverter.
5.
If error message remains,
please contact your
installer.
27
Fan fault
1.
Please check if fans are
runing ok.
2.
If fans are runing ok,
please shut down inverter
first and then, restart it.
3.
If fans are stop runing or
error message remains
after restart the inverter,
please contact your
installer.