background image

VSW20 Wood Stove

12

20300059

INSTAllATION

ST1096
chimney thru fireplace

Flexible Connector

Mantel Shield

Fireplace Adaptor Kit

ST1096

Figure 7 - 
Chimney Connector Through a Fireplace

WAll pASS-ThROughS

Whenever possible, design your installation so the connec-
tor does not pass through a combustible wall.  If you are 
considering a wall pass-through in your installation, check 
with your building inspector before you begin.  Also, check 
with the chimney connector manufacturer for any specific 
requirements.
Accessories are available for use as wall pass-throughs. 
If using one of these, make sure it has been tested and 
listed for use as a wall pass-through.

In  the  united  States,

  the  National  Fire  Protection  As-

sociation (NFPA) has established guidelines for passing 
chimney  connectors  through  combustible  walls.  Many 
building code inspectors follow these guidelines when ap-
proving installations. 

Figure  8

  shows  one  NFPA-recommended  method.  All 

combustible  material  in  the  wall  is  cut  away  from  the 
single-wall connector to provide the required 12” (305 mm) 
clearance. Any material used to close up the opening must 
be noncombustible.
Three other methods are also recommended by NFPA: 

• 

Using a section of double-wall chimney with a 9” (230 
mm) clearance to combustibles. 

• 

Placing a section of chimney connector inside a ventilated 
thimble, which in turn is separated from combustibles 
by 6” (150 mm) of fiberglass insulating material.

• 

Placing a section of chimney connector inside a section 
of 9” (230 mm) diameter, solid-insulated, factory-built 
chimney,  with  2”  (50  mm)  of  air  space  between  the 
chimney section and combustibles.

ST1096
Brick pass thru

Wall Stud

Chimney 

Connector

Floor 

Protection

12” of 

Noncombustible 

Material

ST1097

Figure 8 -
A Brick Pass thru - Approved In the United States

In Canada,

 The Canadian Standards Association has es-

tablished installation guidelines.  The following illustration  
shows one method, in which all combustible material in the 
wall is cut away to provide the required 18” (460 mm) clear-
ance for the connector.  The resulting space must remain 
empty.  A flush-mounted sheet metal cover may be used 
on one side only.  If covers must be used on both sides, 
each cover must be mounted on noncombustible spacers 
at least 1” (25 mm) clear of the wall.
Your  local  dealer  or  your  local  building  inspector  can 
provide  details  for  other  approved  methods  of  passing 
a chimney connector through a combustible wall in your 
area.  In Canada, this type of installation must conform to 
CAN/CSA-B365, Installation Code for Solid Fuel Burning 
Appliances and Equipment.  

NOTE: 

Do  not  vent  your  Challenger  into  a  factory-built 

(zero-clearance)  fireplace.  These  appliances  and  their 
chimneys  are  specifically  designed  as  a  unit  for  use  as 
fireplaces. It may void the listing or be hazardous to adapt 
them for any other use.

dO  NOT  CONNECT  AN  ChAllENgER  TO  ANY  AIR 
dISTRIbuTION duCT OR SYSTEM.

Summary of Contents for VSW20

Page 1: ...perly installed a house fire may result To reduce the risk of fire follow the installation instructions Failure to follow instructions may result in property damage bodily injury or even death Contact...

Page 2: ...e and proper care it will provide you with many years of service This manual contains valuable instructions on the installation and operation of your Vermont Castings stove You will also find useful i...

Page 3: ...such fuels contain chemicals known to the State of California to cause cancer birth defects and other reproductive harm California Health and Safety Code Sec 25249 6 WARNING HOT GLASS WILL CAUSE BURN...

Page 4: ...wood fuel The stove is intended for operation only with the door fully closed Do not install any products not specified for use with this stove SAFETY INFORMATION BEFORE INSTALLATION OF YOUR APPLI AN...

Page 5: ...aft is obtained operate only with doors closed and open slowly when re fueling This will reduce or eliminate smoke from entering the room Attempts to achieve higher output rates that exceed heater des...

Page 6: ...pending on how the stove is operated type and moisture content of fuel and other factors Maximum burn times are achieved under different operating conditions than are maximum heat outputs 2 These valu...

Page 7: ...r combustion because of insufficient air infiltration into the building Such air enters a home through unsealed cracks and openings Kitchen or bath exhaust fans can compete with the stove for availabl...

Page 8: ...h a chimney can take quite a while to warm up and the stove performance will likely be disappointing The best solution to an oversize flue problem is the installation of an insulated steel chimney lin...

Page 9: ...te is a flammable and when ignited make an extremely hot fire within the flue system which can damage the chimney and overheat adjacent combustible material To reduce the amount of creosote that may f...

Page 10: ...connector sections Consult your local dealer about these special pieces ST242 Chimney connector 12 13 99 djt Secure the Single wall Connector to a Prefabricated Chimney For prefabricated chimneys fol...

Page 11: ...ctor Flue Collar Flue Flue Liner Thimble ST1094 Figure 5 Freestanding Installation Chimney Connection ST1095 chimney connector above fireplace Chimney Connector Shields Check These Clearances Mantel S...

Page 12: ...is separated from combustibles by 6 150 mm of fiberglass insulating material Placing a section of chimney connector inside a section of 9 230 mm diameter solid insulated factory built chimney with 2...

Page 13: ...east 16 from the front of the stove and at least 8 from the sides and rear Figure 10 In Canada a noncombustible floor protector is required under the heater also The floor protector must extend 18 457...

Page 14: ...offer the required protection of 8 203 mm on either side Optional 3 76 mm short legs may be used only on such hearths that meet the width and depth requirements out lined previously under floor prote...

Page 15: ...8 SSW40 clearances 10 08 Top Vent out the Back Wall with Minimum 2 Vertical Figure 12 Clearances to Combustibles ST1008 Clearance to Combustibles UL 1482 and ULC s627 Minimum clearance to combustible...

Page 16: ...a chimney fire All of the installation characteristics that adversely affect chimney draft also promote creosote condensation Consequently you can minimize creosote accumulation with an effective chim...

Page 17: ...ideal coal bed of 1 25 mm to 2 51 mm should be established to achieve optimum performance 6 This unit is designed to function most effectively when air is allowed to circulate to all areas of the fir...

Page 18: ...ith the use of a readily available oven cleaner 5 Never put substances which can ignite explosively in the unit since even small explosions in confined areas can blow out the glass 6 This unit has an...

Page 19: ...ems 3 BURN ONLY SEASONED WOOD Avoid burning wet or green wood Seasoned wood has been dried for at least one year 4 A small hot fire is preferable to a large smoldering one that can deposit creosote wi...

Page 20: ...013 8 Secondary Air Tube Middle 1 63D1012 9 Secondary Air Tube Back 1 63D1011 10 C Cast Combo VSW20 1 63D1007 11 C Cast top VSW20 1 63D1009 12 Shield Rear Adjustable Air 1 63D1039 13 Shield Rear Outsi...

Page 21: ...fficient space in the firebox Adjust the air control setting to desired setting Page 17 i Note The lower the air control setting the longer the burn time of your firewood 2 What type of wood is best t...

Page 22: ...r or not there is sufficient air in your home for your stove curtail from using those appliances known to consume the air where possible or open a window or door to allow air to enter the home b Envir...

Page 23: ...e Warranty will also be void if the appliance is not operated and maintained according to the operating instructions supplied with the appliance and does not extend to 1 firebox burner assembly damage...

Page 24: ...VSW20 Wood Stove 24 20300059 MHSC 149 Cleveland Drive Paris Kentucky 40361 www mhsc com...

Reviews: