Vermont Castings Vigilant II Homeowner'S Installation And Operating Instructions Manual Download Page 9

9

Vermont Castings Vigilant

2000898

VIGILANT

24" 

(610mm)

Max.

ST687

chimney connector

8/7/01   djt

Prefabricated 

Chimney

Single-wall 

Chimney Connector

Chimney 

Connector 

Heat Shield

Bottom 

Heat 

Shield

ST687

Fig. 9

  Chimney connector heat shields may be used to re-

duce clearances when single-wall connectors are used.

Clearances With Double Wall Chimney 

Connectors And Rear Stove Heat Shields

When a rear heat shield is used on the stove and a 
double wall chimney connector is used, the rear clear-
ance is 15

¹⁄₂

" (395 mm) and the chimney connector 

clearance is 12" (300 mm). 

 

Clearances With Single-wall Chimney 

Connectors, Connector Shields And Rear 

Stove Heat Shields

Use of both stove and chimney connector heat shields, 
on single-wall connectors, in top-exiting installations 
reduces the required clearance. (Fig. 10)

13" (330mm)

18"

(460mm)

ST688

Vigilant

clearances

parallel,

rear heat shield,

chimney connector

heat shield

8/7/01   djt

ST688

Fig. 10

  Minimum clearance, chimney connector heat shield, 

rear heat shield.

Protected Walls

A properly constructed wall shield may be used to 
change an unprotected wall to a protected wall, allow-
ing the clearances given in the right half of the Clear-
ance Chart.
Wall shields should be 
constructed of 24 gauge 
or heavier sheetmetal, 
1/2” noncombustible insu-
lation board, or common 
brick laid on flat (3

¹⁄₂

" side 

down).  Shields must be 
spaced out from the com-
bustible wall or ceiling 1" 
on noncombustible spac-
ers.  The spacers should 
not be directly behind the 
stove or chimney connec-
tor.
Air must be able to flow 
between the wall and the 
shield.  At least one-half 
(50%) of the bottom 1" 
of the shield should be 
open and the shield must 
stop 1" from the ceiling.  
Protect the top opening 
with metal screening to 
prevent objects from fall-
ing behind the shield.
Rear wall shields must extend 18" above the top of the 
stove or to within 1" of the ceiling, must be centered 
behind the stove, and must be a minimum of 48" (1220 
mm) wide by 48" high.  
Side wall shields must be 48" (1220 mm) wide by 44" 
high, and must extend 15" (380 mm) beyond the front 
of the stove as measured from a point on the wall that 
is on the same plane as the door glass.

ST248

wall shield construction

12/14/99   djt

Air Flow

Wall Shield

Noncom-

bustible 

Spacer and 

Fasteners

Drywall

Stud Wall Fram-

ing

Air Flow

ST248

Fig. 11 

 Wall shield con-

struction.

Summary of Contents for Vigilant II

Page 1: ...se SAFETY NOTICE IF THIS APPLIANCE IS NOT PROPERLY INSTALLED OPERATED AND MAINTAINED A HOUSE FIRE MAY RESULT TO REDUCE THE RISK OF FIRE FOLLOW THE INSTALLATION INSTRUCTIONS FAILURE TO FOLLOW INSTRUCTI...

Page 2: ...ur Authorized Vermont Castings Dealer anytime you have a particular question about your stove or its performance Be assured that your cast iron Vermont Castings stove or replace has been made with the...

Page 3: ...ption obtained under laboratory conditions and on average ef ciencies These values are based on operation in building code conforming homes under typical winter climate condi tions in New England If y...

Page 4: ...eight due largely to a difference in temperature between the gases inside the chimney and gases out side the chimney Because gas expands when heated warm gases inside the chimney weigh less than cool...

Page 5: ...necessary for this type of installation The chimney should extend at least 3 feet above the highest point where it passes through a roof and at least 2 feet higher than any portion of a building with...

Page 6: ...VE OR INSERT TO A CHIMNEY FLUE SERVING ANOTHER APPLIANCE Chimney Size When out tted with the standard 6 150 mm ue col lar The Vigilant II Coal Stove is designed to perform well when vented through ues...

Page 7: ...ove will be in either a parallel or a corner instal lation not both Use only the part of the chart that ap plies to your installation Note Side clearances do not apply to corner installations Measure...

Page 8: ...mum clearance parallel installation rear heat shield For rear exiting stoves both rear and side clearances are determined by the heat from the stove provided that the connector does not pass near a co...

Page 9: ...ed to change an unprotected wall to a protected wall allow ing the clearances given in the right half of the Clear ance Chart Wall shields should be constructed of 24 gauge or heavier sheetmetal 1 2 n...

Page 10: ...mm Clearance to Combustibles in Front of Stove 1 A ceiling heat shield 24 610 mm in diameter and suspended 1 25 mm from the ceiling must surround the chimney con nector in installations in which the...

Page 11: ...mm D 16 406 mm E 12 305 mm F 2 51 mm to either side of connector Fig 12 Minimum oor protection requirements ST689 oor protector must meet the same requirements as for standard legs Floor Protection f...

Page 12: ...market which have been tested and listed speci cally for use as wall pass throughs Use only these tested and listed accessories for wall pass throughs The National Fire Protection Association NFPA has...

Page 13: ...cessories The Removable Handle The removable handle is inserted into the front door stub or the damper handle stub when you want to open or close the doors or change the position of the damp er The ha...

Page 14: ...Coal Stove Freestanding If the chimney connector must pass through a combustible wall to reach the chimney follow the recommendations in the Wall Pass Through sec tion ST243 thinble connection 12 13...

Page 15: ...e Watch these points If there is a combustible mantel or trim check the stove and chimney connector clearances in the Clearance Chart Use the necessary combination of mantel trim and connector heat sh...

Page 16: ...nformation about the ash content of the coal he sells The Vigilant II Coal Stove is designed to burn anthracite hard coal or bituminous coal soft coal Do not burn other fuels As shipped from the facto...

Page 17: ...is between 400 and 700 F although temperatures slightly outside of this range may be expected However if tempera tures go above 700 F for extended periods decrease the air supply move the thermostat...

Page 18: ...smaller and draft problems can result Avoid draft problems when the outside temperature is 35 F or higher by operating your stove with the damper open to keep ue temperatures high If draft problems o...

Page 19: ...striker screw one turn and re tight ening the small locking nut Keep making adjustments slowly until the setting is right The handle should resist slightly as it is turned to the closed position and t...

Page 20: ...e plate and then slide it toward the front of the stove so the end with the shorter offset will be behind the iron The cover in the lower reback will be inserted into the opening and pushed to the lef...

Page 21: ...side up on a level work sur face 2 Remove the two retainer clips Carefully remove the old glass 3 Examine the gasketing Worn gasketing should be replaced Remove the old gasketing Cut new gasket ing to...

Page 22: ...y two weeks during the heating season to determine if a soot buildup has occurred If soot has accumulated it should be removed to reduce the risk of a chimney re Fly ash carried from the fuel bed by d...

Page 23: ...if any appear to be corroded Is the door handle adjusted so the doors close tight ly Instructions for adjusting the handle are given in the Maintenance Section Draft Problems If the draft in the chim...

Page 24: ...m Description Part Number Item Description Part Number CFM Corporation reserves the right to make changes in design materials speci cations prices and discontinue colors and products at any time witho...

Page 25: ...n Cover w Handle 1601027 32 Shaker Handle 1600903 33 Ashpan 1400927 34 Ashdoor 1305045 35 Front Door Handle Assembly 5004237 36 Ashpan Bracket 1601039 37 Ashdoor Hinge 1305046 38 Ashdrop 1305044 39 Bo...

Page 26: ...26 Vermont Castings Vigilant 2000898...

Page 27: ...s 1 This warranty is transferable however proof of original purchase is required 2 CFM Corporation offers no warranty on chipping of enamel surfaces Inspect your Vigilant II Coal Stove prior to accept...

Page 28: ...2695 Meadowvale Blvd Mississauga Ontario Canada L5N 8A3 800 668 5323 www cfmcorp com CFM Corporation...

Reviews: