Vermont Castings Vigilant II Homeowner'S Installation And Operating Instructions Manual Download Page 13

13

Vermont Castings Vigilant

2000898

Horizontal runs of chimney connectors should slope 
upward 1/4” per foot going from the stove toward the 
chimney.  The recommended maximum length of a 
horizontal run is 3 feet.  The total length of chimney 
connector should be no longer than 8 feet to prevent 
the cooling of flue gases.  
In cathedral ceiling installations, a prefabricated 
chimney should be brought down to within 8 feet of 
the stove.  The whole chimney connector should be 
exposed and accessible for inspection and cleaning.  
Never pass a chimney connector through a combustible 
ceiling.

Installation Procedures

Setting Up the Stove

Our stoves are heavy and require at least two people 
to move and set them up.  To make the job a bit easier, 
you may lift off the loading doors and remove the grid-
dle, grates, and ashpan.  Do not try to move the stove 
alone as the stove can be damaged by mishandling.
Place the stove close to its final position before install-
ing the stove legs.
The griddle has not been painted in order to allow 
cooking directly on its surface.  In order to protect the 
surface from rust during shipping, a coating of oil has 
been applied.  Be sure to wash the griddle thoroughly 
with soap and water.  As the stove is used, the griddle 
will gradually darken to match the color of the stove.
Your Vigilant Coal Stove arrives completely assembled 
except for the installation of the legs and handle holder, 
and the assembly of the removable handle.  The only 
tool needed are a 9/16” wrench, used to tighten the leg 
bolts.
So that you can easily secure the first section of chim-
ney connector pipe to the stove, three holes have been 
drilled in the flue collar and three sheetmetal screws are 
included in the hardware package.
If you have ordered any accessories such as heat 
shields, they will come with their own installation 
instructions.  Generally speaking, nothing more compli-
cated than a screwdriver is involved in the installation of 
accessories.

The Removable Handle

The removable handle is inserted into the front door 
stub or the damper handle stub when you want to open 
or close the doors, or change the position of the damp-
er.  The handle is removed when not being used so it 
will not get hot, and stored in the handle holder installed 
on one of the front legs.
To assemble the handle, pass the long threaded screw 
through the ceramic shaft and into the bright metal 
insert.  Tighten until snug; do not overtighten.

Chimney Connector Dampers

Because of the draft requirements of our stoves, we do 
not recommend the use of an in-flue damper.  Not only 
is this an unnecessary restriction in the flue, but it is an 
additional surface directly in the path of the flue gases 
upon which deposits can form, creating a potential haz-
ard.  Combustion air entering your Vigilant Coal stove 
is controlled effectively by the thermostat, so no flue 
damper is required.

The Chimney Connector

Assembly

•  Assemble the chimney connector beginning at the 

flue collar of the stove, keeping the crimped ends 
towards the stove.  Using the holes in the flue collar 
as guides, drill 1/8” holes in the bottom of the first 
section of chimney connector, and secure it to the 
flue collar with #10 x 1/2” sheetmetal screws.

• Align the seams of the individual sections.  Secure 

each joint between sections of chimney connector, 
including telescoping joints, with at least three sheet-
metal screws.  

• Secure the chimney connector to the chimney.  In-

structions for various installations follow.

• Be sure the installed stove and chimney connector are 

correct distances from nearby combustible material.

Your dealer may offer a variety of specialty pipe pieces 
to simplify the installation, including slip pipes and 
thimble sleeves that can be used to form telescoping 
joints between sections of chimney connector.  Tele-
scoping joints may eliminate the need to cut individual 
sections of connector.

ST693

Vigilant

freestanding 

installation

8/01

Chimney

Elbow

Slip Pipe

Standard 

Connector

Oval to Round 

Connector

Flue Collar

Thimble

Flue 

Liner

Flue

ST693

Fig. 17

  An exploded view of the chimney connection in a 

freestanding masonry installation.

Summary of Contents for Vigilant II

Page 1: ...se SAFETY NOTICE IF THIS APPLIANCE IS NOT PROPERLY INSTALLED OPERATED AND MAINTAINED A HOUSE FIRE MAY RESULT TO REDUCE THE RISK OF FIRE FOLLOW THE INSTALLATION INSTRUCTIONS FAILURE TO FOLLOW INSTRUCTI...

Page 2: ...ur Authorized Vermont Castings Dealer anytime you have a particular question about your stove or its performance Be assured that your cast iron Vermont Castings stove or replace has been made with the...

Page 3: ...ption obtained under laboratory conditions and on average ef ciencies These values are based on operation in building code conforming homes under typical winter climate condi tions in New England If y...

Page 4: ...eight due largely to a difference in temperature between the gases inside the chimney and gases out side the chimney Because gas expands when heated warm gases inside the chimney weigh less than cool...

Page 5: ...necessary for this type of installation The chimney should extend at least 3 feet above the highest point where it passes through a roof and at least 2 feet higher than any portion of a building with...

Page 6: ...VE OR INSERT TO A CHIMNEY FLUE SERVING ANOTHER APPLIANCE Chimney Size When out tted with the standard 6 150 mm ue col lar The Vigilant II Coal Stove is designed to perform well when vented through ues...

Page 7: ...ove will be in either a parallel or a corner instal lation not both Use only the part of the chart that ap plies to your installation Note Side clearances do not apply to corner installations Measure...

Page 8: ...mum clearance parallel installation rear heat shield For rear exiting stoves both rear and side clearances are determined by the heat from the stove provided that the connector does not pass near a co...

Page 9: ...ed to change an unprotected wall to a protected wall allow ing the clearances given in the right half of the Clear ance Chart Wall shields should be constructed of 24 gauge or heavier sheetmetal 1 2 n...

Page 10: ...mm Clearance to Combustibles in Front of Stove 1 A ceiling heat shield 24 610 mm in diameter and suspended 1 25 mm from the ceiling must surround the chimney con nector in installations in which the...

Page 11: ...mm D 16 406 mm E 12 305 mm F 2 51 mm to either side of connector Fig 12 Minimum oor protection requirements ST689 oor protector must meet the same requirements as for standard legs Floor Protection f...

Page 12: ...market which have been tested and listed speci cally for use as wall pass throughs Use only these tested and listed accessories for wall pass throughs The National Fire Protection Association NFPA has...

Page 13: ...cessories The Removable Handle The removable handle is inserted into the front door stub or the damper handle stub when you want to open or close the doors or change the position of the damp er The ha...

Page 14: ...Coal Stove Freestanding If the chimney connector must pass through a combustible wall to reach the chimney follow the recommendations in the Wall Pass Through sec tion ST243 thinble connection 12 13...

Page 15: ...e Watch these points If there is a combustible mantel or trim check the stove and chimney connector clearances in the Clearance Chart Use the necessary combination of mantel trim and connector heat sh...

Page 16: ...nformation about the ash content of the coal he sells The Vigilant II Coal Stove is designed to burn anthracite hard coal or bituminous coal soft coal Do not burn other fuels As shipped from the facto...

Page 17: ...is between 400 and 700 F although temperatures slightly outside of this range may be expected However if tempera tures go above 700 F for extended periods decrease the air supply move the thermostat...

Page 18: ...smaller and draft problems can result Avoid draft problems when the outside temperature is 35 F or higher by operating your stove with the damper open to keep ue temperatures high If draft problems o...

Page 19: ...striker screw one turn and re tight ening the small locking nut Keep making adjustments slowly until the setting is right The handle should resist slightly as it is turned to the closed position and t...

Page 20: ...e plate and then slide it toward the front of the stove so the end with the shorter offset will be behind the iron The cover in the lower reback will be inserted into the opening and pushed to the lef...

Page 21: ...side up on a level work sur face 2 Remove the two retainer clips Carefully remove the old glass 3 Examine the gasketing Worn gasketing should be replaced Remove the old gasketing Cut new gasket ing to...

Page 22: ...y two weeks during the heating season to determine if a soot buildup has occurred If soot has accumulated it should be removed to reduce the risk of a chimney re Fly ash carried from the fuel bed by d...

Page 23: ...if any appear to be corroded Is the door handle adjusted so the doors close tight ly Instructions for adjusting the handle are given in the Maintenance Section Draft Problems If the draft in the chim...

Page 24: ...m Description Part Number Item Description Part Number CFM Corporation reserves the right to make changes in design materials speci cations prices and discontinue colors and products at any time witho...

Page 25: ...n Cover w Handle 1601027 32 Shaker Handle 1600903 33 Ashpan 1400927 34 Ashdoor 1305045 35 Front Door Handle Assembly 5004237 36 Ashpan Bracket 1601039 37 Ashdoor Hinge 1305046 38 Ashdrop 1305044 39 Bo...

Page 26: ...26 Vermont Castings Vigilant 2000898...

Page 27: ...s 1 This warranty is transferable however proof of original purchase is required 2 CFM Corporation offers no warranty on chipping of enamel surfaces Inspect your Vigilant II Coal Stove prior to accept...

Page 28: ...2695 Meadowvale Blvd Mississauga Ontario Canada L5N 8A3 800 668 5323 www cfmcorp com CFM Corporation...

Reviews: