Vermont Castings Vigilant II Homeowner'S Installation And Operating Instructions Manual Download Page 17

17

Vermont Castings Vigilant

2000898

3.  Continue building up the fire until there is a thick bed 

of hot embers on the grates.  

IMPORTANT:

  Don’t hurry this part of the burn.  Inad-

equate preheating of the chimney system is the most 
common cause of poor coal stove performance.

NOTE:

  The cast iron plates in your Vigilant will “sea-

son” as they heat and cool over a period of time.  The 
thermal shock of very rapid temperature changes can 
cause the cast iron to crack.  NEVER build a roaring fire 
in a cold stove.
4.  Add a moderate layer  (1” - 2” ) of coal.  When this 

is burning well, indicated by a blue flame just above 
the first layer, you may add coal layer by layer. Be 
sure each new layer is burning well before adding 
the next layer.

CAUTION: Hot while in operation.  Keep children, 
clothing, and furniture away.  Contact may cause 
skin burns.

5.  Coal may be loaded to the top of the front grill, and 

to within one inch of the exhaust ports in the top of 
the left and right side plates.  Keep the coal level at 
least an inch below the exhaust ports.  

SAFETY NOTE:  Do not burn garbage or flammable 
fluids such as gasoline, naphtha, or engine oil.  Do 
not use charcoal lighter fluid or any flammable liq-
uid to kindle or re-establish a fire in your coal burn-
ing stove.  Also, never use self-starting charcoal 
briquettes.  The volatile gases given off by these 
materials when heated may explode if ignited.
CAUTION:

 Follow these instructions carefully to get the 

safest, most efficient results with your stove.  Failure 
to follow these instructions may result in a dangerous 
chimney or house fire.

Daily Operation

Surface Thermometer

Use a surface thermometer to monitor stove perfor-
mance.
The Vigilant’s surface temperature, determined by plac-
ing a stove thermometer in the middle of the griddle, 
can provide helpful information about how the stove is 
performing.  

ST698

Vigilant

surface therm

08/01

Surface Thermometer

ST698

Fig. 23

  A stove thermometer can provide helpful information 

about how the stove is performing.

The normal range of operating temperatures is between 
400° and 700° F, although temperatures slightly outside 
of this range may be expected.  However, if tempera-
tures go above 700° F for extended periods, decrease 
the air supply (move the thermostat lever to the right) 
and slow the fire to avoid overfiring.
When starting a new fire, or after re-loading the stove, 
leave the damper open until the surface temperature 
reaches at least 500° F.  Do not close the damper on a 
fire before it is well-established.  
If the surface temperature drops below 400° F, revive 
the fire by one of the following: 
 

• Increase the air supply  by moving the thermo 
  stat lever to the left.

 

• Open the damper.

 

• Clear ash from the grates and empty the ash 
  pan.

 

• Re-load the stove.

 

• Add a layer of untreated charcoal or NON- 
  SELF-STARTING charcoal briquettes.

 

• If the coal needs to be re-ignited, try placing a  
  small amount of very dry, finely split kindling  
  on top of the coal bed.  The heat produced  
  by the burning kindling will increase the draft,  
  and the improved draft will increase the air flow  
  through the coal bed to create better conditions  
  for ignition.

Internal Damper

The internal damper provides operating flexibility  
Operate the Vigilant with the damper open when start-
ing the fire, when re-building the fire after a long burn, 
or when burning a small fire with moderate heat output.  
Close the damper only after establishing a strong fire 
and a good draft by burning the stove with the damper 
open. 
Because installation characteristics vary, the time nec-
essary to establish a good draft may also vary, from ap-
proximately 5 to 30 minutes or more.  Exterior chimneys 
are generally more difficult to heat up,  and may require 
the longest period of time. 
On large and/or outside chimneys, the damper may 
always need to be open for the flue to be sufficiently 
warmed so that it will support an adequate draft.  Even 
if this is necessary, the Vigilant will operate effectively.
Be sure to open the damper and run the stove for a few 
minutes before opening either the griddle or the front 
doors.  This will direct extra heat to the flue to increase 
the draft, and will clear exhaust gases from the baffle 
system.  Do not leave doors and griddle open simulta-
neously to avoid having gases escape.

Summary of Contents for Vigilant II

Page 1: ...se SAFETY NOTICE IF THIS APPLIANCE IS NOT PROPERLY INSTALLED OPERATED AND MAINTAINED A HOUSE FIRE MAY RESULT TO REDUCE THE RISK OF FIRE FOLLOW THE INSTALLATION INSTRUCTIONS FAILURE TO FOLLOW INSTRUCTI...

Page 2: ...ur Authorized Vermont Castings Dealer anytime you have a particular question about your stove or its performance Be assured that your cast iron Vermont Castings stove or replace has been made with the...

Page 3: ...ption obtained under laboratory conditions and on average ef ciencies These values are based on operation in building code conforming homes under typical winter climate condi tions in New England If y...

Page 4: ...eight due largely to a difference in temperature between the gases inside the chimney and gases out side the chimney Because gas expands when heated warm gases inside the chimney weigh less than cool...

Page 5: ...necessary for this type of installation The chimney should extend at least 3 feet above the highest point where it passes through a roof and at least 2 feet higher than any portion of a building with...

Page 6: ...VE OR INSERT TO A CHIMNEY FLUE SERVING ANOTHER APPLIANCE Chimney Size When out tted with the standard 6 150 mm ue col lar The Vigilant II Coal Stove is designed to perform well when vented through ues...

Page 7: ...ove will be in either a parallel or a corner instal lation not both Use only the part of the chart that ap plies to your installation Note Side clearances do not apply to corner installations Measure...

Page 8: ...mum clearance parallel installation rear heat shield For rear exiting stoves both rear and side clearances are determined by the heat from the stove provided that the connector does not pass near a co...

Page 9: ...ed to change an unprotected wall to a protected wall allow ing the clearances given in the right half of the Clear ance Chart Wall shields should be constructed of 24 gauge or heavier sheetmetal 1 2 n...

Page 10: ...mm Clearance to Combustibles in Front of Stove 1 A ceiling heat shield 24 610 mm in diameter and suspended 1 25 mm from the ceiling must surround the chimney con nector in installations in which the...

Page 11: ...mm D 16 406 mm E 12 305 mm F 2 51 mm to either side of connector Fig 12 Minimum oor protection requirements ST689 oor protector must meet the same requirements as for standard legs Floor Protection f...

Page 12: ...market which have been tested and listed speci cally for use as wall pass throughs Use only these tested and listed accessories for wall pass throughs The National Fire Protection Association NFPA has...

Page 13: ...cessories The Removable Handle The removable handle is inserted into the front door stub or the damper handle stub when you want to open or close the doors or change the position of the damp er The ha...

Page 14: ...Coal Stove Freestanding If the chimney connector must pass through a combustible wall to reach the chimney follow the recommendations in the Wall Pass Through sec tion ST243 thinble connection 12 13...

Page 15: ...e Watch these points If there is a combustible mantel or trim check the stove and chimney connector clearances in the Clearance Chart Use the necessary combination of mantel trim and connector heat sh...

Page 16: ...nformation about the ash content of the coal he sells The Vigilant II Coal Stove is designed to burn anthracite hard coal or bituminous coal soft coal Do not burn other fuels As shipped from the facto...

Page 17: ...is between 400 and 700 F although temperatures slightly outside of this range may be expected However if tempera tures go above 700 F for extended periods decrease the air supply move the thermostat...

Page 18: ...smaller and draft problems can result Avoid draft problems when the outside temperature is 35 F or higher by operating your stove with the damper open to keep ue temperatures high If draft problems o...

Page 19: ...striker screw one turn and re tight ening the small locking nut Keep making adjustments slowly until the setting is right The handle should resist slightly as it is turned to the closed position and t...

Page 20: ...e plate and then slide it toward the front of the stove so the end with the shorter offset will be behind the iron The cover in the lower reback will be inserted into the opening and pushed to the lef...

Page 21: ...side up on a level work sur face 2 Remove the two retainer clips Carefully remove the old glass 3 Examine the gasketing Worn gasketing should be replaced Remove the old gasketing Cut new gasket ing to...

Page 22: ...y two weeks during the heating season to determine if a soot buildup has occurred If soot has accumulated it should be removed to reduce the risk of a chimney re Fly ash carried from the fuel bed by d...

Page 23: ...if any appear to be corroded Is the door handle adjusted so the doors close tight ly Instructions for adjusting the handle are given in the Maintenance Section Draft Problems If the draft in the chim...

Page 24: ...m Description Part Number Item Description Part Number CFM Corporation reserves the right to make changes in design materials speci cations prices and discontinue colors and products at any time witho...

Page 25: ...n Cover w Handle 1601027 32 Shaker Handle 1600903 33 Ashpan 1400927 34 Ashdoor 1305045 35 Front Door Handle Assembly 5004237 36 Ashpan Bracket 1601039 37 Ashdoor Hinge 1305046 38 Ashdrop 1305044 39 Bo...

Page 26: ...26 Vermont Castings Vigilant 2000898...

Page 27: ...s 1 This warranty is transferable however proof of original purchase is required 2 CFM Corporation offers no warranty on chipping of enamel surfaces Inspect your Vigilant II Coal Stove prior to accept...

Page 28: ...2695 Meadowvale Blvd Mississauga Ontario Canada L5N 8A3 800 668 5323 www cfmcorp com CFM Corporation...

Reviews: