14
DVA4136 Series Direct Vent Gas Fireplace
10010270
FP1012
Top vent max run
1/25/00 djt
20' (6m)
7.5' (2.3m)
Pipe Straps
Every 3’ (914mm)
Firestop/Zero
Clearance Sleeve
Pipe
Straps Every
3’ (914mm)
FP1012
Fig. 14
Support straps for horizontal runs.
•
If a 90° elbow is used in the horizontal vent run
(level height maintained) the maximum horizontal
vent length is reduced by 36” (914 mm). This does
not apply if the 90° elbows are used to increase or
redirect a vertical rise.
Example:
According to the chart the maximum
horizontal vent length in a system with a 7.5’ (2.3 m)
vertical rise is 20’ (6 m) and if a 90° is required in
the horizontal vent it must be reduced to 17’ (5.2 m).
In Figure 16, Dimension A plus B must not be
greater than 17’ (5.2 m).
Since it is very important that the vent-
ing system maintain its balance between
the combustion air intake and the flue
gas exhaust, certain limitations as to vent
configurations apply and must be strictly
adhered to.
The vent graph showing the relationship between verti-
cal and horizontal side wall venting will help to deter-
mine the various dimensions allowable.
Minimum clearance between vent pipes
and combustible materials is one 1”
(25mm) on top, bottom and sides unless
otherwise noted.
When the vent termination exits through foundations
less than 20” (508 mm) below siding outcrop, the vent
pipe must flush up with the siding.
It is always best to locate the fireplace in such a way
that minimizes the number of offsets and horizontal vent
length of vent pipe from the flue collar of the fireplace to
the face of the outer wall.
7.5'
(2.3m)
A
B
A + B = 17' (5.2m) Max.
1 x 90° elbow in horizontal plane = 3’ (914mm)
FP1238
Fig. 16
Maximum vent run with elbows.
•
The maximum number of 45° elbows permitted per
installation is six (6). These elbows can be installed
in either the vertical or horizontal run.
•
For each 45° elbow installed in the horizontal run,
the length of the horizontal run MUST be reduced by
18” (457 mm). This does not apply if the 45° elbows
are installed on the vertical part of the vent system.
•
The maximum number of elbow degrees in a system
is 270°. (Fig. 17)
2'
(610 mm)
FP1821
horizontal plane
10/07
1'
(305 mm)
5' (1.5 m)
2'
(610 mm)
FP1821
Fig. 15
Horizontal vent run.
Minimum Horizontal
Vent Run
Maximum Horizontal
Vent Run
Vertical Sidewall Applications
Horizontal plane means no vertical rise exists on this
portion of the vent assembly.
•
The maximum number of 90° elbows per side wall
installations is three (3).
•
Must have a one foot (1’/305 mm) minimum verti-
cal vent before attaching a 90° elbow to the unit.
The maximum horizontal vent run before the
termination is 24” (610 mm). (Fig. 15)
Vertical Sidewall Installation
Twist Lock Pipe
STEP 1
Locate vent opening on the wall. It may be necessary
to first position the fireplace and measure to obtain hole
location. Depending on whether the wall is combustible
or noncombustible, cut opening to size. (Fig. 18)
For combustible walls first frame in opening.