DVA4136 Series Direct Vent Gas Fireplace

10010270

Lighting & Operating Instructions

     

 

 

For Fireplaces equipped with AF4000 Gas Valve

  A.  This fireplace is equipped with an ignition device  
    which automatically lights the pilot. 

DO NOT

 try to  

    light the pilot by hand.
  B. 

BEFORE OPERATING

, smell all around the  

    appliance area for gas. Be sure to smell next to  
    the floor because some gas is heavier than the  
    air and will settle on the floor.
   

What to do if you smell gas

    •  Do not try to light any appliance.
    •  Do not operate any electrical switch.
    •  Do not use any phone in your building.

For Your Safety, Read the Following Warnings  

before Lighting the Appliance

    •  Immediately call your gas supplier from  
      a neighbor’s phone. Follow the gas    
      suppliers instructions.
    •  If you cannot contact your gas supplier call  
      the Fire Department

  C. Do not use this appliance if any part has been  
    under water. Immediately call a qualified service  
    technician to inspect the appliance and replace  
    any part of the control system and any gas control  
    that has been under water.

1.  Turn the remote switch to the OFF position.
2.  Turn OFF all electrical power to the fireplace if 

service is required.

3.  Open the lower access panel.
4.  Turn the shut-off valve on the flexible gas line to 

the OFF position.

FP297A

     

Warning:

  If you do not follow these instructions exactly, a fire or explosion may  

     

  result, causing property damage, personal injury and loss of life.

Lighting Instructions

Turning Off the Gas to the Appliance

FP297A

INSTA VENT FREE

UVHB26 GAS SUPPLY 

7/1/98

1. 

STOP! 

Read the safety information above before 

continuing.

2.  This appliance is equipped with an ignition device 

which  automatically lights the pilot. 

DO NOT

 try to 

light the pilot by hand.

3.  Access the gas control by removing the side cover 

access door on the left side of the unit.

4.  Turn the remote switch, if used, OFF. Turn the 

wireless remote, if used, OFF.

5.  Wait five (5) minutes to clear out any gas. 

Then smell for gas, including near the floor. 
If you smell gas, STOP. Follow instruction B 
in the safety warnings above. If you do not 
smell gas, go on to the next step.

6.  Close the access door.
7.  If the appliance will not operate, follow the 

instructions TURNING OFF THE GAS TO 
THE APPLIANCE, and call your service 
technician or gas supplier.

1/2” Gas Supply

1/2” NPT x 3/8” Flare 

Shut-Off Valve

3/8” Flex Line

(From Valve)

Valve in the 

“ON”

 position

������
������������
����

“S” Connection 

Connect to Module

Spark to Pilot

Pilot Assembly

Pilot Gas Connection

Side or Back

“I” Connection

Connect to 

Module

Main Valve Internal Solenoid 

Connection 

Green & White Wires

Outlet 

Pressure Tap

Pilot Internal 

Solenoid 

Connection

Orange & 

white Wires

Inlet Pressure 

Tap

Pilot Adjustment 

Screw 

Step Motor 
Connector 

Summary of Contents for TrimWorks DVA4136

Page 1: ...w the gas suppliers instructions If you cannot reach your gas supplier call the re department WARNING IF THE INFORMATION IN THIS MANUAL IS NOT FOLLOWED EXACTLY A FIRE OR EXPLOSION MAY RESULT CAUSING P...

Page 2: ...Applications Installations 18 Venting Components 20 Operating Instructions Glass Information 21 Louvre Removal 21 Window Frame Assembly Removal 21 Glass Cleaning 22 Installation of Logs Lava Rock Emb...

Page 3: ...lace DVA4136 Certi ed To ANSI Z21 88b 2008 CSA 2 33b 2008 Vented Gas Fireplace Heaters 12 This replace requires adequate ventilation and combustion air to operate properly 13 This replace must not be...

Page 4: ...ent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OB...

Page 5: ...1162 mm 3 2 8 2 2 m m 5 8 1 6 m m 6 4 1 6 4 5 m m 20 524 mm 20 524 mm 7 191 mm 22 575 mm 7 178 mm Dia 4 102 mm Dia 5 8 16 mm 2 51 mm 6 168 mm 6 152 mm 24 610 mm 6 152 mm 1 25 mm 40 1016 mm 36 914 mm 4...

Page 6: ...s and legs may be installed at any height and width around the appliance When using paint or lacquer to nish the mantel such paint or lacquer must be heat resistant to prevent discoloration Clearance...

Page 7: ...t and secure it rmly in place Gas Speci cations Max Min Gas Input Input Model Fuel Control BTU h BTU h DVA4136IFN Natural Gas 6 Volt Hi Lo 38 000 7 100 DVA4136IFP Propane 6 Volt Hi Lo 38 000 7 100 Gas...

Page 8: ...stalled must be elec trically connected and grounded in accord ance with local codes or in the absence of local codes with the current CSA C22 1 Canadian Electrical Code For USA installations follow l...

Page 9: ...tor To Pilot Ignitor To Pilot Flame Sensor Battery Back Up Pack Red Black Learn Button Remote Off Switch Continuous Pilot ON OFF Switch Optional ON OFF Switch Step Motor Main Flame Orange Brown Red Ye...

Page 10: ...m General Venting There must not be any obstruction such as bushes garden sheds fences decks or utility buildings within 24 610 mm from the front of the termination hood Do not locate termination hood...

Page 11: ...tlet 3 91cm 3 91cm J Clearance to nonmechanical air supply inlet 6 15cm for appliances 10 000 6 15cm for appliances to building or the combustion air inlet to any Btuh 3kW 12 30cm for 10 000 Btuh 3kW...

Page 12: ...High Temperature Sealant Hose Clamp FP1471 Fig 10 Apply high temperature sealant to 4 and 7 pipes Outside Corner Inside Corner Termination Clearances Termination clearances for buildings with combust...

Page 13: ...e vent ange Sidewall vent graph showing the relationship between vertical and horizontal dimensions for a Direct Vent ue system Vertical dimension from the oor of the replace to the center of the hori...

Page 14: ...siding It is always best to locate the replace in such a way that minimizes the number of offsets and horizontal vent length of vent pipe from the ue collar of the replace to the face of the outer wal...

Page 15: ...op with 8 sheet metal screws supplied Install restop assembly Fig 19 Zero clearance sleeve is only required for combustible walls STEP 3 Place replace into position Fig 20 Measure the ver tical height...

Page 16: ...127mm 6 172mm FP1474 spacer springs 4 04 djt 4 Flex Vent Pipe Spacer Spring FP1474 Fig 24 Install spacer springs STEP 6 Use appropriate length of pipe sections telescopic or xed and install the horizo...

Page 17: ...e to the wall 7 Level the soil to maintain a 4 102 mm clearance below snorkel Fig 26 Do not back ll around snorkel A clearance of at least 4 102 mm must be maintained between snorkel and the soil If t...

Page 18: ...of vent pipe can be used between elbows Fig 29 7DVCS must be used to support offsets Fig 31 This application will require that you rst determine the roof pitch and use the appropriate starter kit Refe...

Page 19: ...f there is a room above ceiling level restop spacer must be installed on both the bottom and the top side of the ceiling joists If an attic is above ceiling level a 7DVAIS Attic Insulation Shield must...

Page 20: ...l Venting for 7TDVSKV A order 1 12 to 6 12 roof pitch for 7TDVSKV B order 7 12 to 12 12 roof pitch for 7TDVSKV F order at roof Starter Kit for Below Grade Installation Model 7TDVSKS Snorkel Kit Twist...

Page 21: ...down to allow access 1 Turn the replace OFF including the pilot 2 If the unit has been operating allow time for the components to cool 3 If the unit has the standard louvre accessory follow the Louvr...

Page 22: ...denti cation Chart Logs Part ID Rear Log 10010261 M1 Front Log 10010262 M2 Left Log 10010263 M3 Top Center Log 10010264 M4 Top Right Log 10010265 M5 Top Front Log 10010266 M6 It is necessary to period...

Page 23: ...he log over the front left locator pin on the burner Fig 37 Place the left side of the log just inside the stop bracket on the left of the burner Fig 37 Front Log M2 LG512 Figure 40 4 Place the front...

Page 24: ...bottom of the log over the pins on the front log The top of the log will rest against the rear log Fig 41 6 Place the top right log M5 Place the bottom rectangular sot of this log onto the right side...

Page 25: ...25 DVA4136 Series Direct Vent Gas Fireplace 10010270 Figure 44 LG515...

Page 26: ...OFF position FP297A Warning If you do not follow these instructions exactly a re or explosion may result causing property damage personal injury and loss of life Lighting Instructions Turning Off the...

Page 27: ...o push the MODE one more time to OFF NOTE The MODE button will operate ON THERMO OFF in a series that will cycle from ON to THERMO to OFF Fan Mode The control of the fan will be from a button on the h...

Page 28: ...e control will accept the 10 minute setting exit the function setting mode and the LCD display will return to the normal view Pushing TIMER button you can set the ashing clock with the TIMER under the...

Page 29: ...l ash Use UP or DOWN to change the setting of P2 ON Use SET button to enter into next setting S S on LCD will ash Use UP or DOWN to change the setting of P2 OFF Push OK button to enter into next setti...

Page 30: ...ton is being pressed The LED indicator should illuminate on wall transmitters and on off hand held transmitters Buttons should be pressed and held for 1 to 2 seconds to ensure a complete signal is sen...

Page 31: ...rely connected to the terminal labeled S on the control module Fig 45 Make sure the orange and white leads from the module are securely connected to the terminals labeled PILOT on the valve body Fig 4...

Page 32: ...d red leads from the battery pack or the AF4000 110H L module are securely connected to the red and black leads from the motor drive or H L latching solenoid located on the valve body red to red and b...

Page 33: ...n gasket with mixer tube mounting plate 6 Reassemble into the replace the burner housing assembly the burner tube assembly and the fettle in reverse order Mixer Tube Replacement Conversion to NG ONLY...

Page 34: ...mixer tube supplied with conversion kit using screw from old mixer tube Refer to Table 2 to set shutter opening 4 Using 2 screws install new mixer tube and new spring assembly into burner housing asse...

Page 35: ...7 100 38 000 10010519 039 0635 Conversion to Natural Gas Minimum Burner Ori ce Input BTU hr Kit Model Rate Scew Front Part Rear Part Minimum Maximum 10010371 DVA4136IP LSS 00 52 50996 36 10002896 7 1...

Page 36: ...ide 2 Let replace cool if it has been running 3 Remove window frame assembly Refer to Window Frame Assembly Removal section 4 Remove logs 5 Vacuum burner compartment especially around ori ce primary a...

Page 37: ...56 8 Remove the glass noting the orientation of the gas ket on the glass Fig 57 9 Remove the bad bulb s and install new bulb s Fig 58 10 Reassemble the replace in reverse order Light bulb replacement...

Page 38: ...n design materials speci cations prices and discontinue colors and products at any time with out notice DVA4136 Units GFYN5J0 2 3 4 8 15 18a b 30 40 36 41 10270 DVA4136 parts 10 07 5 43 14 13 37 27 1a...

Page 39: ...t not shown 10002896 16b Or ce Rear Burner 51 067 LP not shown 57598 17a Ori ce Front Burner 52 0635 Nat not shown 50996 17b Ori ce Front Burner 59 041 LP not shown 57177 18a Ori ce Pilot Nat 10002268...

Page 40: ...Flue Pipe 10002237 39 Burner Tray Gasket 20012346 40 Relief Plate Assembly Burner Base 10004192 41 Plate Relief w Gasket Assembly 10002429 42 Shield Heat Pilot 10010144 43 24 Wire Harness 8 Pin 8 Wire...

Page 41: ...onic fan speed control box on bottom of replace base lining up mounting holes with screw studs Fasten fan speed control box with 10 24 hex nuts Option B The speed control can be installed in an electr...

Page 42: ...replace Kit Color DV4136CRSS Sandstone DV4136CRR Colonial Red DV4136CRG Silver Grey DV4136CRB Classic Black DV4136CRCG Country Grey Ceramic Refractory Panels Take care when handling the refractory pa...

Page 43: ...shop Ifuponinspection thedamageisfoundtobethefaultofthemanufacturer repairs will be authorized at no charge to the customer parts and or labor Any part and or component replaced under the provisions o...

Page 44: ...cy Ratings Model EnerGuide Ratings Steady State D O E Fireplace Ef ciency Fan ON AFUE DVA4136IFN 70 81 68 2695 Meadowvale Blvd Mississauga Ontario Canada L5N 8A3 800 668 5323 www cfmcorp com CFM Corpo...

Reviews: