7
3-90-20306760
Vermont Castings • Stardance SDDVTSB Installation Manual_R10 • 04/18
Parallel Installation
Minimum Clearance and Flue Centerline
Stove Clearances
A 4" (102 mm)
B 4" (102 mm)
Pipe Centerlines
C
15-1/2" (395 mm)
D 9" (229 mm)
Figure 3 - Parallel installation, minimum back and side
clearances, and flue centerlines.
ST128b
Stardance
flue centerline
9/28/00 djt
C
L
C
L
B
D
C
A
Wall Centerline from Floor
Effective Minimum
Wall Thimble
56" (1480 mm) (HHT Pipe)
Centerline
52" (1378 mm) DuraVent Pipe)
Figure 5 - Minimum wall centerline.
Direct Vent Only
ST131b
Stardance
wall thimble
9/28/00 djt
A
Hearth Requirements
The Stardance heater must be installed on rigid flooring.
When the heater is installed directly on any combustible
surface other than wood flooring, a metal or wood panel
extending the full width and depth of the unit must be used
as the hearth. There are no other hearth requirements.
Wall & Ceiling Clearances
A Rear Wall
4" (102 mm)
B Minimum Clearance
45-1/4" (1154 mm)
C Minimum Alcove Height
72" (1830 mm)
D Maximum Alcove Depth
48" (1220 mm)
Sidewall Clearance
4" (102 mm)
*
needed for installing DuraVent Minimum Vent Kit #2792 or HHT Minimum Vent Kit #SLP-FSSK.
Figure 6 - Dimensions and clearances to ceiling or alcove.
Direct Vent Only
A
C
D
ST101b
Stardance
Direct Vent
Min. Clrnc
9/28/00 djt
B
Corner Installation
Minimum Clearance and Flue Centerline
Stove Clearances
A 4" (102 mm)
Pipe Centerlines
B
14-1/2" (370 mm)
Figure 4 - Corner installation, minimum corner clearances
and flue centerline.
ST129b
Stardance
corner specs
9/28/00 djt
A
A
B
B