Vermont Castings SDDVTBDSB Installation & Operating Manual Download Page 4

4

3-90-20306760

Vermont Castings • Stardance SDDVTSB Installation Manual_R10 • 04/18

Requirements for the Commonwealth of 

Massachusetts

All gas fitting and installation of this heater shall only be done 

by a licensed gas fitter or licensed plumber.
For all side wall horizontally vented gas fueled equipment 

installed in every dwelling, building or structure used in whole 

or in part for residential purposes, including those owned or 

operated by the Commonwealth and where the side wall 

exhaust vent termination is less than seven (7) feet above 

finished grade in the area of the venting, including but not 

limited to decks and porches, the following requirements 

shall be satisfied:

Installation of Carbon Monoxide Detectors

At the time of installation of the side wall horizontal vented 

gas fueled equipment, the installing plumber or gas fitter shall 

observe that a hard wired carbon monoxide detector with an 

alarm  is installed on each additional level of the dwelling, 

building  or  structure  served  by  the  side  wall  horizontal 

vented gas fueled equipment. It shall be the responsibility 

of  the  property  owner  to  secure  the  services  of  qualified 

licensed professionals for the installation of hard wired carbon 

monoxide detectors.

In the event that the side wall horizontally vented gas fueled 

equipment is installed in a crawl space or an attic, the hard 

wired carbon monoxide detector with alarm and battery 

back-up may be installed on the next adjacent floor level.

In the event that the requirements of this subdivision can not 

be met at the time of completion of installation, the owner shall 

have a period of thirty (30) days to comply with the above 

requirements; provided, however, that during said thirty (30) 

day period, a battery operated carbon monoxide detector with 

an alarm shall be installed.

Approved Carbon Monoxide Detectors

Each carbon monoxide detector as required in accordance 

with the above provisions shall comply with NFPA 720 and 

ANSI/UL 2034 listed and IAS certified.

Signage

A metal or plastic identification plate shall be permanently 

mounted to the exterior of the building at a minimum 

height of eight (8) feet above grade directly in line with 

the exhaust vent terminal for the horizontally vented gas 

fueled heating appliance or equipment. The sign shall 

read, in print size no less than one-half (1/2) inch in size, 

“GAS VENT DIRECTLY BELOW, KEEP CLEAR OF ALL 

OBSTRUCTIONS".

Inspection

The state or local gas inspector of the side wall horizontally 

vented gas fueled equipment shall not approve the installation 

unless, upon inspection, the inspector observes carbon 

monoxide detectors and signage installed in accordance with 

the provisions of 248 CMR 5.08(2)(a)1 through 4.

Exemptions

The following equipment is exempt from 248 CMR 5.08(2)

(a)1 through 4:
•  The equipment listed in Chapter 10 entitled “Equipment 

Not Required To Be Vented" in the most current edition of 

NFPA 54 as adopted by the Board; and

• 

Product Approved side wall horizontally vented gas fueled 

equipment installed in a room or structure separate from 

the dwelling, building or structure used in whole or in part 

for residential purposes.

Manufacturer Requirements

Gas Equipment Venting System Provided

When the manufacturer of Product Approved side wall 

horizontally vented gas equipment provides a venting system 

design or venting system components with the equipment, 

the instructions provided by the manufacturer for installation 

of the equipment and the venting system shall include:
•  Detailed instructions for the installation of the venting 

system design or the venting system components; and

•  A complete parts list for the venting system design or 

venting system.

Gas Equipment Venting System NOT Provided

When the manufacturer of a Product Approved side wall 

horizontally vented gas fueled equipment does not provide 

the parts for venting the flue gases, but identifies “special 

venting systems", the following requirements shall be 

satisfied by the manufacturer:

•  The referenced “special venting system" instructions shall 

be included with the appliance or equipment installation 

instructions; and

•  The “special venting systems" shall be Product Approved 

by the Board, and the instructions for that system shall 

include a parts list and detailed installation instructions.

A copy of all installation instructions for all Product Approved 

side wall horizontally vented gas fueled equipment, all venting 

instructions, all parts lists for venting instructions, and/or all 

venting design instructions shall remain with the appliance 

or equipment at the completion of the installation.

Stardance Direct Vent

Certified to: ANSI Z21.88-2014 / CSA 2.33-2014 Vented 

Gas Heaters 

Proposition 65 Warning:

 Fuels used in gas, wood-

burning or oil fired appliances, and the products of 

combustion of such fuels, contain chemicals known to 

the State of California to cause cancer, birth defects and 

other reproductive harm.

California Health & Safety Code Sec. 25249.6

Summary of Contents for SDDVTBDSB

Page 1: ...ot reach your gas supplier call the fire department Installation and service must be performed by a qualified installer service agency or the gas supplier WARNING FIRE OR EXPLOSION HAZARD Failure to f...

Page 2: ...Limited Lifetime Warranty 60 Important Safety Information 3 Massachusetts residents only 4 Pre Installation 5 Stove Dimensions 5 Installation Requirements 6 Clearance Requirements 6 Parallel Installa...

Page 3: ...f Conventional venting systems Natural Vent take air from the room for combustion and vent the exhaust vertically through the roof to the atmosphere This appliance is approved for bedroom installation...

Page 4: ...KEEP CLEAR OF ALL OBSTRUCTIONS Inspection The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless upon inspection the insp...

Page 5: ...ct Vent Stove Dimensions Figure 1 Stardance dimensions Weight Fully assembled 202 lbs See Figure 3 4 for Flue Collar Centerline Dimensions 26 3 4 680 mm 25 1 2 648 mm 14 1 2 355 mm 3 76 mm C L 12734 S...

Page 6: ...se the wallpaper to shrink or may adversely affect the binders in the wallpaper adhesive WARNING Due to high temperatures the heater should be located out of traffic and away from furniture and draper...

Page 7: ...the heater is installed directly on any combustible surface other than wood flooring a metal or wood panel extending the full width and depth of the unit must be used as the hearth There are no other...

Page 8: ...al gas and 4 500 feet 1 370 m for LP Gas Maintain the manifold pressure at 3 5 w c for Natural Gas and 10 0 w c for LP Gas HIGH ELEVATIONS Input ratings are shown in BTU per hour and are certified wit...

Page 9: ...ow flames producing soot or flames lifting off of the ember bed ports Restrictor Plate Adjustment Remove the screw in the back wall of the firebox Install restrictor plate as shown in Figure 9 with cu...

Page 10: ...es to keep in mind are shown in Figure 11 Important All vent clearances must be maintained Check your vent termination clearances against Figures 11 and 12 The vent should be placed so that people can...

Page 11: ...00 BTU h 3kW and 100 000 BTU h 30kW 36 91cm for appliances 100 000 BTU h 30kW 6 15cm for appliances 10 000 BTU h 3kW 9 23cm for appliances 10 000 BTU h 3kW and 50 000 BTU h 15kW 12 30cm for appliances...

Page 12: ...s Min 12 305 mm for vinyl sidewalls O 8 2 4 m Min O P V V V Figure 12 Termination clearances DMin of Termination caps x 3 CMax 2 termination caps x DActual NOTE Termination in an alcove space spaces o...

Page 13: ...Steel Chimney Conv Kit A 6 5 8 8 5 8 46DVA KCA Steel Chimney Conv Kit B 6 5 8 10 1 2 46DVA KCB Steel Chimney Conv Kit C 6 5 8 13 46DVA KCC Masonry Chimney Conversion Kit 46DVA KMC Vertical Termination...

Page 14: ...e Rheostat mounts to the valve cover plate The assembly includes a snapstat which automatically turns the fan On or Off above or below approximately 109 The Rheostat also provides a range of fan speed...

Page 15: ...the rheostat tightening with a wrench Do not over tighten Attach the control knob to the rheostat shaft Use the wire tie to secure the fan and rheostat wire harnesses together Figure 17 Attach blower...

Page 16: ...nt systems Rear Top Vent Vertical Side wall Horizontal sections of this vent system require a minimum of 3 76 mm clearances to combustibles at the top of the flue and 1 25 mm clearance at the sides an...

Page 17: ...ace Figure 21 General Information The Stardance is approved for installation only with the vent components listed in the Approved Vent System Components section in this manual Follow the vent componen...

Page 18: ...ns Vertical sections of SLP pipe must be supported every 8 ft The SLP firestop includes tabs that may be used to secure vertical sections The vent support or plumber s strap spaced 120 apart may be us...

Page 19: ...brought to the edge of the cap base Disassemble Vent Sections To disassemble any two pieces of pipe rotate either section Figure 27 so that the seams on both pipe sections are aligned Figure 28 They...

Page 20: ...nstallation NOTE For all top vent vertical through the roof installations install the supplied flue restrictors onto the top edge of the firebox flue adapter according to the Vertical Side wall Instal...

Page 21: ...rovided 6 Level the soil to maintain a 4 clearance below the snorkel 7 If the foundation is recessed use extension brackets not supplied to fasten the lower portion of the snorkel Fasten the brackets...

Page 22: ...nimum of an 8 2 5 m vertical rise is required Figure 38 Two sets of 45 elbow offsets may be used within the vertical sections From 0 to a maximum of 8 2 5 m of vent pipe can be used between elbows Fig...

Page 23: ...ge Opening Roof Pitch H Min Ft Roof Pitch H Min Ft Flat to 6 12 1 0 Over 11 12 to 12 12 4 0 Over 6 12 to 7 12 1 25 Over 12 12 to 14 12 5 0 Over 7 12 to 8 12 1 5 Over 14 12 to 16 12 6 0 Over 8 12 to 9...

Page 24: ...he vent safety switch can result in carbon monoxide CO poisoning and possible death For U S installations The venting system must conform with local codes and or the current National Fuel Gas Code ANS...

Page 25: ...LL DAMAGED LOGS 2 Install the rear log by mating the notch on the bottom of the log with the raised notch on the back left side of the ember bed Figure 44 Ensure the cutout in the right side of the lo...

Page 26: ...Install the wall thermostat or switch in the desired location and run the wires to the stove location Terminate these leads with 1 4 female connectors 2 Connect the thermostat wires to the valve Figur...

Page 27: ...to the command center Figure 52 The connection is labeled Wall Switch Unplug the male and female connectors and connect the two 2 low voltage wires provided Run wire to desired location on wall Up to...

Page 28: ...12905 Conversion instructions are provided with each kit and in this manual CAUTION This appliance should only be connected by a qualified gas technician Test to confirm manifold pressures as specifie...

Page 29: ...UNCTION BOX IN FIREPLACE PLUG IN CONNECTOR WHITE BLACK BLACK WHITE GREEN Opt Blower Opt Aux Control Board RF Receiver ON OFF Button Pilot Black Thermopile Red Thermopile Sensor Ignitor Sparker Convers...

Page 30: ...screen fits securely in place NOTE It is the responsibility of the installer to ensure the barrier is affixed to the stove at the time of installation CERTIFIED SAFETY BARRIER DANGER HOT GLASS WILL C...

Page 31: ...58 If flame patterns are incorrect turn the heater off Contact your dealer or a qualified gas technician for assistance Do not operate the heater until the pilot flame is correct Follow regular maint...

Page 32: ...ormed 3 Open control access panel 4 Push in gas control knob slightly and turn clockwise to OFF Do not force 5 Close control access panel If knob does not pop up when released stop and immediatelycall...

Page 33: ...res defective 1 Check wall switch and wires for proper connections Jumper wire across terminals at wall switch if burner comes on replace defective wall switch If okay jumper wires across wall switch...

Page 34: ...all your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department C Use only your finger to push in the master switch...

Page 35: ...r switch to the ON position Within eight 8 seconds it will beep once This indicates the system is ready 5 Press ON button Sparker will spark and pilot flame will light 6 Once pilot flame is establishe...

Page 36: ...Flame Height Settings Low battery Indication for Transmitter Child Proof Lock out LCD Backlight Security Codes 16 Countdown 6 hr Timer Standard Thermostatic Control Mode Smart Mode Thermostat Auto Fla...

Page 37: ...set ups at the command center Cold Climate Option The Signature Command System is designed to operate in either Standing Pilot or Intermittent Pilot mode The Standing Pilot Mode is best for colder cl...

Page 38: ...emperature from 40 F to 99 F Lo and HI will be displayed when the room temperature is lower than 40 F or higher than 99 F respectively Turning the Stove Off There are three ways to turn the stove off...

Page 39: ...ttery icon indicator is displayed The radio icon will be shown when the transmitter is sending a signal The low battery indication icon will be shown when the battery voltage is low The child proof ic...

Page 40: ...nds During the 10 seconds press the OFF button on the transmitter to learn Another two beeps will be given to confirm a successful learning Figure 65 Resetting the Transmitter If the transmitter is no...

Page 41: ...down on the arrow buttons to exit TIMER mode and shut off the stove Thermostat Mode Figure 67 NOTE The Command Center buttons will disable when thermostat is being used Press the THERMO button to set...

Page 42: ...Press the ON up and OFF down button to increase decrease the blower speed Press the fan button again to confirm the speed setting If the stove is on the blower speed will take effect right away if th...

Page 43: ...Low Battery Detection When low battery condition occurs the transmitter will turn off the stove Battery voltage is checked every one minute When the battery voltage is low the LCD displays a low batt...

Page 44: ...ies Plug the AC plug to AC mains Repair or replace the AC Board Replace the AC Board Replace the Control Board or Command Center Sparking is happening elsewhere under the pilot re install replace the...

Page 45: ...engulfing the thermopile and the other reaching to the main burner Burner Inspect area around the injector Remove any lint or foreign material with a brush or vacuum Burner Flame The flames from the b...

Page 46: ...his kit The installation is not proper and complete until the operation of the converted appliance is checked as specified in the manufacturer s instructions supplied with the kit CAUTION The gas supp...

Page 47: ...p H I LO H I LO LP Configuration Natural Gas Configuration CO141 O ring configuration 6 07 Red O ring Visible Red O ring NOT Visible Figure 79 Pilot ST350 Jefferson air shutter adj 3 20 00 djt Figure...

Page 48: ...orifice Refer to Table 2 The air shutter is factory set according to Table 3 and should not need adjustment The air shutter opening may be verified by measuring as shown in Figure 86 CO142 air shutte...

Page 49: ...35 SDVTSC models Leak check the system using a gas leak detector solution Relight the main burner in both the HI and LO positions to verify proper burner ignition and operation Conversion is complete...

Page 50: ...Conversion to LP Input BTU h Model Kit Orifice Part Minimum Maximum SDDVT 20012735K 1 45 mm 20308650 21 000 25 000 SDVTSC 20308380 Conversion to Natural Gas Input BTU h Model Kit Orifice Part Minimum...

Page 51: ...ed Clean areas to be painted with a wire brush and be sure to cover the logs burner and valve assembly glass and frame assembly Apply the paint sparingly two light coats of paint will give better resu...

Page 52: ...y pipe must be checked to confirm that they are unblocked and in good condition Check the Gas Flame Regularly To ensure that the stove is operating properly check the flames periodically to confirm th...

Page 53: ...onal Thermopile Black Black Millivolt Gas Valve St124b on off switch wiring 1 11 00 djt TP TH TP TH Thermostat Optional Thermopile Black Black St124c Thermostat wiring 1 11 00 djt TP TH TP TH FAN Stra...

Page 54: ...nversion NG LP Plug in Connector Control Board to Command Center OFF LO LED ON HI Master Switch Command Center Optional Wall Switch Plug in Connector Stepper Motor to Control Board NOTE Wall switch wi...

Page 55: ...TSCBS Biscuit SDDVTBSSB Biscuit SDDVTCSBSSB Biscuit End Manufacturing Date October 2015 SDVTSCBM Majolica Brown SDDVTBMSB Majolica Brown SDDVTCSBMSB Majolica Brown End Manufacturing Date October 2015...

Page 56: ...Top Classic Black 30001276 Biscuit 30003305 Bordeaux 30006752 Brown Majolica 30004897 4 Front Operable Door Classic Black 30001496 Biscuit 30003302 Bordeaux 30006753 Brown Majolica 30004899 5 Door Rig...

Page 57: ...24D0808 Y 21 Electrode Ignitor w Cable SIT24 10001297 22 Thermopile 18 RS SRV26D0566 Y 23 Tubing Pilot w Fittings 1 8 x 24 26D0665 Y 24 Pilot Ori ce Top Convertible SDDVT NG 62 37D0022 SDDVT LP 35 200...

Page 58: ...K Y Switch Bracket 53821K Starter Pipe 20307738K Rear Shroud SDVT SC SDDVT 20003802 Rear Shroud Assembly SDDVTCS 20300122 Fiberglass Gasket 1 4 1 00 1203560 Y Magnet Door Use super glue Silicone to at...

Page 59: ...area is required Remote Controls SDDVT The remote control allows you to turn the heater on or off from anywhere in the room Refer to Page 53 for wiring diagrams These remote controls are for use with...

Page 60: ...the sale of the product by an independent authorized HHT dealer distributor whichever occurs earlier However the warranty shall commence no later than 24 months following the date of product shipment...

Page 61: ...d exterior surface finishes may occur This is not a flaw and is not covered under warranty Damage to printed plated or enameled surfaces caused by fingerprints accidents misuse scratches melted items...

Page 62: ...venting installation LIMITATIONS OF LIABILITY The owner s exclusive remedy and HHT s sole obligation under this warranty under any other warranty express or implied or in contract tort or otherwise sh...

Page 63: ......

Page 64: ...tallation Manual_R10 04 18 Based on CSA P 4 1 2015 EFFICIENCY RATINGS MODEL ENERGUIDE RATINGS STOVE EFFICIENCY PERCENTAGE D O E AFUE PERCENTAGE SDDVT Series 58 4 66 5 SDVTSC Series 58 4 66 5 352 Mount...

Reviews: