Vermont Castings, Majestic Products RHE Natural Vent Insert
Venting and Installation
Installer must attach red warning plate
with screws supplied with the gas fire-
place insert to the inside of the firebox of
the fireplace into which the gas fireplace
insert is installed.
If a remote wall switch is required for this
fireplace installation, do not wire wall
switch to 120V power supply.
Venting Instructions
TPTH
TH
TP
FP1218a
Fig. 8b ON/OFF switch wiring.
Canadian Installations:
The venting system must be installed in accordance
with the current CSA-B149.1 installation code, and the
authority having jurisdiction.
U.S.A. Installations:
The venting system must be installed in accordance
with the current National Fuel Gas Code, ANSI Z223.1.
Minimum clearances to combustible materials is 1"
(25mm) for B Vent (use of single wall vent is not
allowed).
As with any natural draft appliances, the vent cap must
always extend a minimum of 2' (610mm) above any
structure within a 10' (3m) horizontal plane. (Fig. 9)
2’ Min.
2’
(610mm)
Min.
3’
Min.
0 To 10’
3’
(914mm)
Min.
0 To 10’
Reference
Point
(3m)
AC246a
Fig. 9 Example of the 2', 3', 10' rule.
A minimum 12' (3.7m) vent height is
required to effectively vent this fireplace.
WARNING
This fireplace has been converted for use with
gas only and cannot be used for burning wood
or solid fuels unless all original parts have been
replaced and the fireplace has been re-approved
by the authority having jurisdiction.
Cutting any sheet metal parts of the
fireplace, in which the gas fireplace insert
is to be installed, is prohibited.
If the factory-built fireplace has no gas
access hole(s) provided, an access hole
of 1
¹⁄₂
" (37.5mm) or less may be drilled
through the lower sides or bottom of the
firebox in a proper workmanship like
manner. This access hole must be
plugged with a noncombustible insulation
after the gas supply line has been
installed.
Ensure there are no obstructions to side
air passages of decorative trim once
installed on insert.
1. The Majestic gas inserts are designed for recessed
installations into solid fuel Masonry or Factory Built
Noncombustible fireplaces that have been installed
in accordance with the National, Provincial, State
and local building codes.
2. Measure for minimum fireplace opening requirement
on Page 4 of this installation manual. (If firebrick
[refractory] is removed from a factory built
fireplace in order to gain minimum gas fireplace
insert opening requirements, a minimum of 1/4"
(6.4mm) air space is required between the gas
insert fireplace's outer casing and the inner wall
of the factory built fireplace).
3. To assure top performance, safety and efficiency, all
inserts must be installed with an approved 4"
diameter flue liner, with exception of RHE25, which
should be installed with an approved 3" liner,as per
CSA-B.149 or National Fuel Code ANSI Z223.
WARNING
Some factory built fireplaces have air passages
on face of fireplace for zero clearance capabili-
ties. All trim kits are designed so as to allow
airflow to these passages. Under no circum-
stances should these passages be blocked.