7
20306759
Radiance
®
Direct Vent Gas Heater
PARALLEL INSTALLATION
Minimum Clearance and Flue Centerline
Fig. 3 Parallel installation, minimum back and side clearances,
and flue centerlines.
ST130
ST130
alcove specs
10/99
42" (1070mm)
Min. Alcove Width
48"
(1220mm)
Max. Alcove
Depth
6"
(150mm)
6"
(150mm)
4" (102mm)
ST129
ST129
corner specs
10/99
18"
(457mm)
18"
(457mm)
6"
(150mm)
6"
(150mm)
CL
CL
CORNER INSTALLATION
Minimum Clearance and Flue Centerline
Fig. 4 Corner installation, minimum corner clearances and flue
centerline.
Wall Centerline from Floor
ST131b
Stardance
wall thimble
9/28/00 djt
A
A
Effective Minimum
Centerline
57" (1448 mm)
(HHT Pipe)
55" (1399 mm) (DuraVent Pipe)
ST131b
Fig. 5 Minimum wall centerline.
Direct Vent Only
HEARTH REQUIREMENTS
The Radiance Heater must be installed on rigid flooring.
When the heater is installed directly on any combustible
surface other than wood flooring, a metal or wood panel
extending the full width and depth of the unit must be used
as the hearth. There are no other hearth requirements.
*
needed for installing DuraVent Minimum Vent Kit #2792 or
HHT Minimum Vent Kit #SLP-FSSK.
A
C
D
ST101b
Stardance
Direct Vent
Min. Clrnc
9/28/00 djt
B
A: Rear Wall
4" (102 mm)
B: Min. Clearance
44" (1118 mm)*
C: Min. Alcove Height
72" (1830 mm)*
D: Max. Alcove Depth
48" (1220 mm)
Sidewall Clearance
6" (150 mm)
ST101b
Fig. 6 Dimensions and clearances to ceiling or alcove.
Direct Vent Only
WALL AND CEILING CLEARANCES
PRE-INSTALLATION