TM036 Vermont Gas Fireplace & Gas Log Fire Service Instructions REV: A
D.O.I: 17/01/2008
This document is stored and maintained electronically by
Service. All printed copies not bearing this statement in RED are deemed “uncontrolled”
28
Fault Finding Chart 5.1 & 5.2
(1)
5.1
Is RC
flame level set
on „0‟?
YES
5.2
Remote controller flame
level was set on 0. It must be
set on 1
– 6 for burner to
operate.
Room temp must be > or =
to set temp for burner to
operate.
YES
7
Increase RC set
temp to 1º > room temp &
wait for 1 minute.
Is
RC flame level
„0‟?
Replace remote controller
YES
NO
NO
Note: RC = Remote
Controller
Is
RC flame level
„0‟?
Is RC
room temp > or
= set temp?
NO
Is RC
room temp =
set temp?
YES
YES
NO
Room temp was = set temp
& remote controller turned
burner off. Normal operation.
Did
the burner come
on?
YES
NO
YES
Increase RC flame
level to 6.
Did
the burner come
on?
Notes
(1) When room temp = set temp
burner may be on or off.
(1)
(1)
(1)
NO
NO