Fault Finding Chart 3
YES
NO
3
Is gas
inlet pressure
within spec?
NO
Is
blocked
flue switch
open?
YES
YES
NO
Refer to section on „Checking Inlet Gas
Pressure‟. Refer to Specification Table
for gas pressures.
Refer to section on „Adjusting
the Pilot Flame‟.
Is
Pilotstat knob
operated
correctly?
Pilotstat knob must be held
in the depressed position
and not released until after
the gas valve LED provides
1 flash indication.
Did
gas valve LED
indicate 1
flash?
Replace gas valve.
YES
Adjust pilot flame.
Is pilot
flame adjusted
correctly?
Advise customer.
NO
YES
Does
pilot
ignite?
YES
2
NO
Are
thermopiles
working?
Replace faulty thermopile(s).
NO
Replace gas valve.
YES
NO
Tests 3 & 4
Retry lighting 3 times ensuring
that the Pilotstat knob is not
released until 5 seconds after the
LED gives 1 flash indication.
Does
pilot
ignite?
Did
gas valve LED
indicate 1
flash?
YES
YES
2
NO
NO
Does
gas valve LED
indicate 3 or 8
flashes?
NO
2.1
YES
Does
pilot Stay
lit?
YES
NO
Appliance operational.
2.2
Test 2A for LHEC30
or
Test 2B for RFSDV34