24
20306757
CSDV Series Direct Vent Gas Stove
ELECTRICAL INSTALLATION
ELECTRICAL WIRING
This stove will work without any electrical supply. Electricity
is only needed to operate blower.
NOTE:
If installed in mobile home, fireplace must be bolted
securely to floor.
W
ARNING
Electrical connections should only
be performed by a qualified, licensed
electrician. Main power must be off when
connecting to main electrical power supply
or performing service. All wiring shall be
in compliance with all local, city and state
codes. The appliance, when installed, must
be electrically grounded in accordance
with local codes or in the absence of local
codes, with the National Electrical Code
ANSI/NFPA 70 (latest edition) and Canadian
Electrical Code, CSA C22.1.
CAUTION
Label all wires before disconnecting when
servicing controls. Wiring errors can cause
improper and dangerous operation.
REMOTE WALL MOUNTED SWITCH
A remote wall switch and up to fifteen (15) feet of 18 Ga.
wire may be used with this appliance. Attach the wall
switch in a junction box at the desired location on the
wall.
Figure 33
. Do not extend beyond the wall switch wire
length provided.
NOTE:
Extended lengths of wire may cause the
fireplace not to function properly. Longer length of
wire is permitted if the wire is made out of larger gauge
(diameter) wire. Always check with local code.
Verify proper operation after servicing.
Figure 33 -
Wiring Diagram for Wall Switch
ON
OFF
OPTIONAL REMOTE
WALL SWITCH
PILOT
HI
LO
ON
OFF
TH
TP
TH/TP
ST1148
wiring diagram