background image

VSW40 Wood Stove

60300060

9

INSTALLATION

WALL PASS-ThRUS

Whenever  possible,  design  your  installation  so  the 
connector does not pass through a combustible wall.  If 
you  must  use  a  wall  pass-through  in  your  installation, 
check with your building inspector before you begin and 
construct it in accordance with local building codes.  Also, 
check with the chimney connector manufacturer for any 
specific requirements.

Accessories are available from your dealer for use as wall 
pass-throughs.  If using one of these, make sure it has been 
tested and listed for use as a wall pass-through.

All combustible material in the wall is cut away a sufficient 
distance  from  the  single-wall  connector  to  provide  the 
required 12" (305 mm) clearance for the connector.  Any 
material  used  to  close  up  the  opening  must  be  non-
combustible.

The following wall pass-through methods 

may be

 approved 

in your area:

  Use a section of listed factory-built chimney with a 

nine-inch clearance to combustibles.

  Place a chimney connector pipe inside a ventilated 

thimble, which is then separated from combustibles 
by 6" (152 mm) of fiberglass insulating material.

  Place  a  chimney  connector  pipe  inside  a  section 

of  listed  solid-insulated,  factory-built  chimney, 
with an inside diameter 1" (51 mm) larger than the 
chimney connector and having 1" (25 mm) or more 
of insulation and maintaining a minimum 2 inch air 
space between the outer wall of the chimney and 
combustibles.

ST1009
wall pass thru

Chimney 
Connector

12" 

(305 mm)

12" 

(305 mm)

ST1009

Figure 2 - 
Wall Pass-thru Enclosed with 
Noncombustible Materials

do not connect the heater to any air distribution duct 
or system.
In  Canada:   

The  Canadian  Standards Association  has 

established  different  guidelines.    Figure  11  shows  one 
method, in which all combustible material in the wall is cut 
away to provide the required 18" (450 mm) clearance for 
the connector.  The resulting space must remain empty.
A flush mounted sheet metal cover may be used 

on one 

side only.

  If covers must be used on both sides, each cover 

must be mounted on non-combustible spacers at least 1" 
(25 mm) clear of the wall.  Your Vermont Castings dealer 
or your local building inspector can provide details of other 
approved methods of passing a chimney connector through 
a combustible wall.  In Canada, this type of installation must 
conform  to  CAN/CSA-B365.    Installation  Code  for  Solid 
Fuel Burning Appliances and Equipment.

NOTE:  

Do not vent your stove into a factory-built (zero-

clearance) fireplace. These appliances and their chimneys 
are specifically designed as a unit for use as fireplaces.  
It may void the listing or be hazardous to adapt them for 
any other use.

ST1010
hollow wall pass thru 

Sheet Metal Cover 
(This Side Only)

18" (450 mm)
Empty Space All Around the 
Chimney Connector

ST1010

Figure 3 -
Hollow wall pass-thru

Summary of Contents for Challenger VSW40

Page 1: ...ly installed a house fire may result To reduce the risk of fire follow the installation instructions Failure to follow instructions may result in property damage bodily injury or even death Contact lo...

Page 2: ...NSTALLER Please leave these instructions with the appliance OWNER Please retain these instructions for future reference WARNING Proposition 65 Warning Fuels used in gas woodburning or oil fired applia...

Page 3: ...n individual use depending on how the stove is operated type and moisture content of fuel and other factors Maximum burn times are achieved under different operating conditions than are maximum heat o...

Page 4: ...icipal or provincial fire authority for information on how to handle a chimney fire Have a clearly understood plan to handle a chimney fire In the event of a chimney fire turn air control to closed po...

Page 5: ...recommended wood load is level with the top of the firebricks Overloading may prevent sufficient air entering the heater to properly fuel the fire Important For optimum heater performance at low burn...

Page 6: ...th 45 or 90 degree bends A bend requires the pipe to be removed for cleaning The stove baffle must be removed when cleaning the chimney see page 15 Chimney sweepings will build up on top of baffle cau...

Page 7: ...fy maintenance If the stovepipe must elbow to enter a chimney locate the elbow about midway between the stovetop and the chimney thimble This configuration lets the smoke speed up before it must turn...

Page 8: ...pe Installation Full Vertical A B C D E F G H I Single Wall Pipe 15 10 26 15 8 20 50 18 8 Flat top model 381 mm 254 mm 660 mm 381 mm 203 mm 508 mm 1270 mm 457 mm 203 mm Double Wall Pipe 13 8 23 12 Fla...

Page 9: ...ng 1 25 mm or more of insulation and maintaining a minimum 2 inch air space between the outer wall of the chimney and combustibles ST1009 wall pass thru Chimney Connector 12 305 mm 12 305 mm ST1009 Fi...

Page 10: ...oint where it passes through the roof and at least 2 610 mm higher than any portion of a building within 10 3 m Figure 5 4 The chimney connector shall not pass through an attic roof space closet conce...

Page 11: ...can generate a chimney fire All of the installation characteristics that adversely affect chimney draft also promote creosote condensation Consequently you can minimize creosote accumulation with an...

Page 12: ...r control 10 08 Low Burn High Burn Figure 6 Air Control Layout ST1013 MAINTENANCE Removing firebrick To remove firebrick liftup from bottom and rotate o u t w a r d Figure 7 ST1018 remove firebrick Fi...

Page 13: ...e c cast baffle is slid back against the steel non removable baffle Replace the rear bricks 1 Ensure appliance is not in operation and is thoroughly cooled 2 Remove door and place on a protected flat...

Page 14: ...UNIT FREE OF CREOSOTE 1 Burn with air control open for several minutes at numerous intervals throughout the day during the heating season being careful not to over fire unit This removes the slight fi...

Page 15: ...6 Handle Assy Ash Pan Door 1 63D0313 7 Ash Pan Door Cast Iron 1 63D0188 8 Fettle 1 63D3002 9 Airwash Cast Iron 1 63D3001 10 Shroud Left 1 63D3117 11 Tube Secondary Top 1 63D3006 12 Tube Air Bottom 4 6...

Page 16: ...ient space in the firebox Adjust the air control setting to desired setting Page 12 i Note The lower the air control setting the longer the burn time of your firewood 2 What type of wood is best to us...

Page 17: ...r or not there is sufficient air in your home for your stove curtail from using those appliances known to consume the air where possible or open a window or door to allow air to enter the home b Envir...

Page 18: ...VSW40 Wood Stove 18 20300060...

Page 19: ...e Warranty will also be void if the appliance is not operated and maintained according to the operating instructions supplied with the appliance and does not extend to 1 firebox burner assembly damage...

Page 20: ...VSW40 Wood Stove 20 20300060 MHSC 149 Cleveland Drive Paris Kentucky 40361 www mhsc com...

Reviews: