Installation Guide

Pressure 

PW Series

TM

Specifications

Media Compatibility

17-4 PH stainless steel

Input Power

12 to 30VDC, 24VAC nom.

Maximum Current Draw

DC:  125mA;  AC:  280mA

Output

3-wire transmitter; user-selectable 4-20mA/0-5V/0-10V

1

Status Indication

Dual color LED

Proof Pressure

2x max. F.S. range

Burst Pressure

5x max. F.S. range

Accuracy at 25°C

2

Ranges A, B, C: ±1% F.S.

3

 

Range D:  ±2% F.S.

3

  

Surge Damping

Electronic; 5-second averaging

Temperature Compensated Range

0° to 50°C (32° to 122°F); 
TC Zero <1.5% of product F.S. per sensor;
TC Span <1.5% of product F.S. per sensor

Sensor Operating Range

-20° to 85°C (-4° to 185°F)

Operating Environment

-10° to 55°C (14° to 131°F); 10-90% RH noncondensing

Long Term Stability

±0.25%

Zero Adjust

Pushbutton auto-zero and digital input (2-position terminal block)

Fittings

psig models:  1/8” NPT female thread, stainless steel 17-4 PH
barg models:  1/8” BSPT female thread, stainless steel 17-4 PH

Physical

White powder-coated aluminum

PRESSURE RANGES

   0-50 psig

5/10/25/50 psid

   0-100 psig

10/20/50/100 psid

   0-250 psig

25/50/125/250 psid

   0-3.5 barg

0.35/0.7/1.75/3.5 bard

   0-7.0 barg

0.7/1.4/3.5/7.0 bard

   0-17 barg

1.7/3.4/8.5/17.0 bard

To conform to EMC Standards, use shielded cabling. Technical information is available from the factory on request or on our 

website (www.veris.com/ce)

1

 Minimum input voltage for 4-20 mA operation:  250 

Ω

 loop (1-5V) = 12 VDC; 500 

Ω

 loop (2-10V) = 15 VDC

   Minimum input voltage for volt operation:  0-5 VDC output = 12 VDC; 0-10 VDC output = 15 VDC

2

 Accuracy combines linearity, hysteresis, and repeatability.

3

 F.S. is defined as full span of selected range in bidirectional mode.

2.2"

(57 mm)

4"

(102 mm)

5.8"

(147 mm)

LOW

HIGH

WET DIFFERENTIAL PRESSURE 

Dimensions

Summary of Contents for PWXN07C

Page 1: ...equences arising out of the use of this material Product Identification Product Overview The PW Series pressure transducer measures the differential pressure across pumps filters heat exchangers and other non corrosive wet media Several operational pressure ranges are available and the analog output is user selectable 4 20 mA 0 5 V or 0 10 V PW Series devices are warranted to meet accuracy specifi...

Page 2: ...to 85 C 4 to 185 F Operating Environment 10 to 55 C 14 to 131 F 10 90 RH noncondensing Long Term Stability 0 25 Zero Adjust Pushbutton auto zero and digital input 2 position terminal block Fittings psig models 1 8 NPT female thread stainless steel 17 4 PH barg models 1 8 BSPT female thread stainless steel 17 4 PH Physical White powder coated aluminum PRESSURE RANGES 0 50 psig 5 10 25 50 psid 0 100...

Page 3: ... psi 100 psi 50 psi 50 psi 0 psi LO PORT 0 psi 50 psi 50 psi 100 psi 100 psi 4 20mA 0 10V 100 psi 50 psi 0 psi 50 psi 100 psi Bidirectional Operation Input Conditions Result Outputs Read DP 20mA 16mA 12mA 8mA 4mA 10V 7 5V 5V 2 5V 0V 17 0 bar 17 0 bar 8 5 bar 8 5 bar 0 bar 0 bar 8 5 bar 8 5 bar 17 0 bar 17 0 bar 17 0 bar 8 5 bar 0 bar 8 5 bar 17 0 bar 20mA 16mA 12mA 8mA 4mA 10V 7 5V 5V 2 5V 0V Outp...

Page 4: ... is read from the low port and the value is usually a negative number This product uses a half wave rectifier power supply If the installer is using a transformer to power the device do not use the same transformer to power other devices utilizing non isolated full wave power supplies Optional Connect the Zero terminals to the digital output contact closure of the control system The Zero input is ...

Reviews: