Installation Guide

Pressure 

PW Series

TM

Installation

Observe precautions for handling static sensitive

devices to avoid damage to the circuitry that

is not covered under the factory warranty.

1.  Find a suitable mounting position near the location to be measured. Mount the PW housing using the self-tapping screws 

provided.

2.  Remove the lid from the housing to reveal the board. Wire the PW terminals to the power source and to the digital control 

system as shown. Configure the jumpers for desired operating parameters. Replace the cover.

JP8
JP7
JP6
JP3
JP2
JP1

ZERO

Analog Reverse/Normal
Port Swap/Normal

Bidirectional/Normal

Fast/Slow Surge Damping
5V/10V Output
mA/Volts Output

POWER

REMOTE ZERO
(Dry Contact)

DIGITAL CONTROL

Analog Input

0-5V/0-10V

or 4-20mA

Optional

Digital Output

POWER SOURCE

12 to 30 VDC/24 VAC

SIGNAL

COM

PW SERIES

/

Range

A

B

C

D

HI PORT

100 psi
100 psi

  50 psi
  50 psi

    0 psi

LO PORT

     0 psi

   50 psi
   50 psi
100 psi
100 psi

4-20mA

0-10V

  +100 psi
     +50 psi
           0 psi
       -50 psi
    -100 psi

Bidirectional Operation

Input Conditions

Result

Outputs Read

DP

20mA
16mA
12mA

  8mA
  4mA

   10V

 7.5V
     5V

2.5V
    0V

17.0 bar
17.0 bar

8.5 bar
8.5 bar

0 bar

0 bar

8.5 bar
8.5 bar

17.0 bar
17.0 bar

  +17.0 bar
     +8.5 bar

           0 bar

       -8.5 bar
    -17.0 bar

20mA
16mA
12mA

  8mA
  4mA

   10V

 7.5V
     5V

2.5V
    0V

Output is either 
mA or V

e.g. PW-04

e.g. PW-08

Range (psi)

Model

PW-03
PW-04
PW-05

A

       50 

100
250

B

25
50

125

C

10
20
50

D
5

10
25

Range (bar)

A

       3.5 

7.0

17.0

B

1.75

3.5
8.5

C

0.7
1.4
3.4

D

0.35

0.7
1.7

e.g. PW-04

e.g. PW-08

Use the Range switch to 

select F.S. differeintial 

pressure.

Model

PW-06
PW-07
PW-08

Jumper

Options

Notes

JP1

Voltage (V) or Current (mA)

JP2

0-10V or 0-5V output span

Use only if JP1 is set to V mode.

JP3

Slow or Fast

Slow mode provides 5 second averaging for 

surge damping.

JP6

Normal or Bidirectional

Normal: 0 to F.S. pressure
Bidirectional:  -F.S. pressure to +F.S. pressure; 

output reads 1/2 when pressure is zero.

JP7

Normal or Port Swap

Reverses polarity of the pressure ports (i.e. 

makes the LO port operate as the HI port and 

vice versa); used when the sensor is incorrectly 

plumbed.

JP8

Normal or Analog Reverse

Normal:  output increases as pressure increases;
Reverse:  output is maximum when pressure 

differential is zero and decreases as pressure 

increases.

Summary of Contents for PWXN07C

Page 1: ...equences arising out of the use of this material Product Identification Product Overview The PW Series pressure transducer measures the differential pressure across pumps filters heat exchangers and other non corrosive wet media Several operational pressure ranges are available and the analog output is user selectable 4 20 mA 0 5 V or 0 10 V PW Series devices are warranted to meet accuracy specifi...

Page 2: ...to 85 C 4 to 185 F Operating Environment 10 to 55 C 14 to 131 F 10 90 RH noncondensing Long Term Stability 0 25 Zero Adjust Pushbutton auto zero and digital input 2 position terminal block Fittings psig models 1 8 NPT female thread stainless steel 17 4 PH barg models 1 8 BSPT female thread stainless steel 17 4 PH Physical White powder coated aluminum PRESSURE RANGES 0 50 psig 5 10 25 50 psid 0 100...

Page 3: ... psi 100 psi 50 psi 50 psi 0 psi LO PORT 0 psi 50 psi 50 psi 100 psi 100 psi 4 20mA 0 10V 100 psi 50 psi 0 psi 50 psi 100 psi Bidirectional Operation Input Conditions Result Outputs Read DP 20mA 16mA 12mA 8mA 4mA 10V 7 5V 5V 2 5V 0V 17 0 bar 17 0 bar 8 5 bar 8 5 bar 0 bar 0 bar 8 5 bar 8 5 bar 17 0 bar 17 0 bar 17 0 bar 8 5 bar 0 bar 8 5 bar 17 0 bar 20mA 16mA 12mA 8mA 4mA 10V 7 5V 5V 2 5V 0V Outp...

Page 4: ... is read from the low port and the value is usually a negative number This product uses a half wave rectifier power supply If the installer is using a transformer to power the device do not use the same transformer to power other devices utilizing non isolated full wave power supplies Optional Connect the Zero terminals to the digital output contact closure of the control system The Zero input is ...

Reviews: