Installation Guide

Pressure 

PW Series

TM

3.  Connect tubing to the high and low ports on the PW.

WET DIFFERENTIAL PRESSURE 

Low 
Port

High 

Port

PSID
PSIG

4.  Connect the other ends of the tubing to a pipe or duct, across the pump, filter, or other pressure differential.

Notes

During operation, the LCD shows two pressure values. The value adjacent to the PSID label shows the differential pressure, while 
the value adjacent to the PSIG label shows the high port gauge pressure. The gauge pressure value is read from the high port if 
JP7 is in the Normal position. If this jumper is in the Port Swap position, the PSIG value is read from the low port, and the value is 
usually a negative number.

This product uses a half-wave rectifier power supply. If the installer is using a transformer to power the device, do not use the 
same transformer to power other devices utilizing non-isolated full-wave power supplies.

Optional:  Connect the Zero terminals to the digital output (contact closure) of the control system. The Zero input is for dry-contact 
only. Do not apply voltage to the Zero terminals.

To use the auto zero function, press and hold the Zero button for 2 seconds or provide contact closure on the auxiliary ‘Remote 
Zero’ terminal to reset the output to zero pressure. To protect the device from accidental zeroing, this feature is only enabled when 
the detected pressure is within 5% of factory calibration.

Installation
(cont.)

LED Blink Codes

LED Color

Status

Solid Green

Normal operation.

Flashing Green

Low > High; use port swap jumper or bidirectional mode.

Solid Red

Differential pressure is too high; select a higher pressure range.

Flashing Red

Gauge pressure over sensor range; reduce line pressure or replace with a higher range device.

Summary of Contents for PWXN07C

Page 1: ...equences arising out of the use of this material Product Identification Product Overview The PW Series pressure transducer measures the differential pressure across pumps filters heat exchangers and other non corrosive wet media Several operational pressure ranges are available and the analog output is user selectable 4 20 mA 0 5 V or 0 10 V PW Series devices are warranted to meet accuracy specifi...

Page 2: ...to 85 C 4 to 185 F Operating Environment 10 to 55 C 14 to 131 F 10 90 RH noncondensing Long Term Stability 0 25 Zero Adjust Pushbutton auto zero and digital input 2 position terminal block Fittings psig models 1 8 NPT female thread stainless steel 17 4 PH barg models 1 8 BSPT female thread stainless steel 17 4 PH Physical White powder coated aluminum PRESSURE RANGES 0 50 psig 5 10 25 50 psid 0 100...

Page 3: ... psi 100 psi 50 psi 50 psi 0 psi LO PORT 0 psi 50 psi 50 psi 100 psi 100 psi 4 20mA 0 10V 100 psi 50 psi 0 psi 50 psi 100 psi Bidirectional Operation Input Conditions Result Outputs Read DP 20mA 16mA 12mA 8mA 4mA 10V 7 5V 5V 2 5V 0V 17 0 bar 17 0 bar 8 5 bar 8 5 bar 0 bar 0 bar 8 5 bar 8 5 bar 17 0 bar 17 0 bar 17 0 bar 8 5 bar 0 bar 8 5 bar 17 0 bar 20mA 16mA 12mA 8mA 4mA 10V 7 5V 5V 2 5V 0V Outp...

Page 4: ... is read from the low port and the value is usually a negative number This product uses a half wave rectifier power supply If the installer is using a transformer to power the device do not use the same transformer to power other devices utilizing non isolated full wave power supplies Optional Connect the Zero terminals to the digital output contact closure of the control system The Zero input is ...

Reviews: