background image

Z207936-0E 

Page 1 of 11 

©2021 Veris Industries   USA 800.354.8556 or +1.503.598.4564  / [email protected] 0921 

 

Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of  Veris Industries, L.L.C. in the USA and/or other countries.

Other companies’ trademarks are hereby acknowledged to belong to their respective owners.

NOTICE

•  This product is not intended for life or safety applications.

•  Do not install this product in hazardous or classified locations.

•  Read and understand the instructions before installing this product.

•  Turn off all power supplying equipment before working on it.

•  The installer is responsible for conformance to all applicable codes.

If this product is used in a manner not specified by the manufacturer, the protection 

provided by the product may be impaired. No responsibility is assumed by the 

manufacturer for any consequences arising out of the use of this material.

Installation Guide

Humidity

Product Identification

Product Overview

The HW2 Protocol Series of humidity sensors for living space is a flexible multisensor platform for use with BAS 
controllers designed to accept BACnet and Modbus outputs. HW2 Protocol Series sensors are available with three 
user interface options: touchscreen, LCD with three buttons and blank. Humidity and temperature sensors are 
included with all HW2 Protocol Series sensors. 

* Replaceable 1% with NIST certificate, 2% with NIST certificate and 2% elements available.

HW2 Protocol Series

Wall Mount Humidity Sensors

Specifications

OPERATING ENVIRONMENT

Input Power

Class 2; 20 to 30 Vdc, 24 Vac, 50 to 60 Hz

Protocol Output

BACnet or Modbus via RS-485, selectable

Operating Temp. Range

0 to 50 °C (32 to 122 °F)

Operating Humidity Range

0 to 95% RH non-condensing

Housing Material

High-impact ABS plastic

Terminal Block Torque

0.5 to 0.6 N-m (0.37 to 0.44 in-lbf)

IP Rating

IP 30

RH TRANSMITTER

HS Sensor

Thin-film capacitive, replaceable

Accuracy

±2% from 10 to 80% RH @ 25°C (77 °F)

Hysteresis

1.5% typical

Stability

±1% @ 20°C (68 °F) annually for 2 years

Output Range

0 to 100% RH

Temperature Coefficient

±0.1% RH/°C above or below 25 °C (77 °F) typical

TEMPERATURE TRANSMITTER

Sensor Type

Solid state, integrated circuit

Accuracy

±0.2 °C (±0.4 °F) typical

Resolution

0.1 °C (0.1 °F)

Range

0 to 50 °C (32 to 122 °F) 

HW2TPxxx

HW2LPxxx

HW2XPxxx

Model

User Interface

RH*

Temperature

Setpoint

Override

HW2TP2A

Touchscreen

X

X

X

X

HW2LP2A

LCD / 3 Buttons

X

X

X

X

HW2XP2A

Blank

X

X

Summary of Contents for HW2 Series

Page 1: ...atform for use with BAS controllers designed to accept BACnet and Modbus outputs HW2 Protocol Series sensors are available with three user interface options touchscreen LCD with three buttons and blan...

Page 2: ...point Temperature humidityorfanspeedselectable Timeoutoverride Displaytimeout Lockoutoverride Touchscreen buttonlockout SETPOINTS Temperature Setpoint Scale 0to50 C 32to122 F or10to35 C 50to95 F max a...

Page 3: ...the cover from the base at the bottom of the device 2 Position the sensor base vertically on the wall 1 35 m 4 5 ft above the floor with the UP arrow facing upward Locate away from windows vents and...

Page 4: ...f an address is selected that conflicts with another device neither device will be able to communicate Address the device as any whole number between and including 1 to 127 Note that zero is not a val...

Page 5: ...o Parity 19200 Baud 1 2 3 4 5 6 7 8 off off on off off off off off None 19200 Baud Unused Modbus Point Map Function Codes Function Code Function 03 Read holding RW registers 04 Read input RO registers...

Page 6: ...en Preservedduringpoweroutages BACnet Descriptions Note In the tables below all properties are read only unless otherwise noted Preserved means the value is maintained through power outages Present_Va...

Page 7: ...y Setpoint BV11 ACTIVE displays temperature setpoint on main screen INACTIVE displays temperature setpoint in upper left corner and current temperature on main screen Screen Color Set MSV 1 Selection...

Page 8: ...ius Temperature value Fahrenheit Celsius Temperature setpoint Menu button RH value Menu button RH value 0 C 100 100 20 20 5 C 23 MenuScreen The menu screen opens when pressing the Menu button on the m...

Page 9: ...eherebyacknowledgedtobelongtotheirrespectiveowners HW2 Protocol Series Installation Guide MenuButtonFunctions cont Touchscreen Operation cont Submenu Only Fan Speed Click this icon to access the fan s...

Page 10: ...s Fahrenheit The Menu Advance button cycles between Temperature RH Fan Speed setpoints and Celsius Fahrenheit adjustment screens in order TemperatureSetpointAdjustment RHSetpointAdjustment ChangeValue...

Page 11: ...s above the limit as stipulated in GB T 26572 Z000057 0B Part Name Hazardous Substances Pb Hg Cd Cr VI PBB PBDE Electronic Environment FriendlyUsePeriod EFUP Table FanSpeedSetpointAdjustment ChangingC...