background image

Z207251-0C 

Page 27 of 42 

©2020 Veris Industries   USA 800.354.8556 or +1.503.598.4564  / [email protected] 0420 

 

Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of  Veris Industries, L.L.C. in the USA and/or other countries.

Other companies’ trademarks are hereby acknowledged to belong to their respective owners.

E34 Series Installation Guide

TM

it is easiest to submit all changes and restart only once when finished with the whole screen. To restart, click the 

System Restart

 

button in the row at the bottom of the screen. The restart takes several seconds, during which the server may lose its connection. 
Messages appear at the top of the screen indicating current status, but do not perform any actions. Simply allow the tool to 
complete the restart cycle. 

The first selection in the GUI is Operating_Mode, which has two choices:

1. Locked:  used for all normal product operation. It is provided as a tool for high-level technical support. The gateway retains 
its current profile configuration when powered. 
2. Discovery mode (default):  deletes profiles and rediscovers them when the device is powered again. The results are the same, 
unless the profile configuration is intentionally altered. Profile selection and discovery are especially important when using 
BACnet or SNMP protocols. For normal operation, always use discovery mode.

The second selection in the GUI is Protocol_Mode, used to select the combination of protocols the product communicates 
with. The E34E supports five protocols, some of which can operate simultaneously. The table below shows which protocols are 
supported in each mode. 

Protocol Mode

Primary Protocol

Ethernet Protocol

RS-485 Protocol

1

BACnet MS/TP

Modbus TCP

BACnet MS/TP

2

BACnet IP

BACnet IP/Modbus TCP

Modbus RTU

3

SNMP

SNMP/Modbus TCP

Modbus RTU

4

Modbus

Modbus TCP

Modbus RTU

 
To select a primary protocol mode, enter the corresponding number into the text field adjacent to the Primary Protocol option and 
click the 

Submit

 button to the right of the text field. A prompt appears at the top of the screen instructing the user to restart the 

system. When finished, the screen refreshes itself with the appropriate fields for the selected mode. 

The next GUI selection, in any protocol mode, is the Upstream_Baud rate selection. If you have selected BACnet MS/TP (mode 1) as 
the primary protocol mode, this value sets the MS/TP baud rate. If you have selected modes 2 or 3 as the primary protocol mode, 
you may not be using the RS-485 interface at all. If so, this setting can be ignored.

If you have selected BACnet IP, SNMP or Modbus mode, the next selection is Modbus_Address, which sets the Modbus address(es) 
for the E34E when access with Modbus RTU with the RS-485 serial connection.

The next selection (in BACnet IP, SNMP or Modbus modes) is Modbus_Parity, which sets the parity of the upstream serial 
connection. If using Modbus RTU protocol, set this to match your Modbus master. If not, ignore this field.

The following sections show the field selections (with factory default values) specific to each of the four Protocol_Modes.  

Gateway Configuration 
(cont.)

Summary of Contents for E34 Series

Page 1: ...ng an RS 485 Modbus protocol E34E models also incorporate Ethernet with support for BACNet IP Modbus TCP and SNMP protocols and include BACnet MS TP serial capability and a sturdy metal enclosure The...

Page 2: ...ference by one or more of the following measures Reorient or relocate the receiving antenna Increase the separation between the equipment and receiver Connect the equipment to an outlet on a circuit d...

Page 3: ...Rate DIP switch selectable 9600 19200 38400 Parity DIP switch selectable NONE ODD EVEN Communication Format 8 data bits 1 start bit 1 stop bit Termination 5 position plug in connector TX TX SHIELD TX...

Page 4: ...ons E34E Models FCC part 15 Class A EN6100 6 4 EN61326 1 Class A Conducted and Radiated Immunity EN 61000 6 2 and EN 61326 1 See Configuration section for details The E34 must be installed in an appro...

Page 5: ...wledgedtobelongtotheirrespectiveowners E34 Series Installation Guide TM Table of Contents Dimensions 6 Product Diagrams 7 Data Outputs 9 Blink Codes for Status LED 10 Installation 11 Wiring 15 Configu...

Page 6: ...emarksof VerisIndustries L L C intheUSAand orothercountries Othercompanies trademarksareherebyacknowledgedtobelongtotheirrespectiveowners E34 Series Installation Guide TM Dimensions E34ABaseBoard 7 3...

Page 7: ...L C intheUSAand orothercountries Othercompanies trademarksareherebyacknowledgedtobelongtotheirrespectiveowners E34 Series Installation Guide TM Product Diagrams Dimensions cont 28 MeterCTAdapterAssem...

Page 8: ...r 3 Control power fuse 600 Vac 500 mA time lag factory replaceable 4 Alive LED E34A models Red green amber LEDs Blink codes are described in the Blink Codes for Status LED section of this document 5 V...

Page 9: ...2 or 3 channels that are adjacent in the panel to a logical meter referred to in the point map as a logical circuit that provides accurate multi phase measurement totals Map these logical circuits by...

Page 10: ...ents Current multi phase average and per phase Current phase angle per branch Real power kW multi phase total and per phase Apparent power kVA multi phase total and per phase Power factor multi phase...

Page 11: ...ons Read understand and follow the instructions before installing this product Turn off all power supplying equipment before working on or inside the equipment Product may use multiple voltage power s...

Page 12: ...kets placed on the two sides for vertical mounting If desired you can move the brackets from the sides to the ends of the housing Loosen the screws on the sides of the E34 that hold the brackets in pl...

Page 13: ...eherebyacknowledgedtobelongtotheirrespectiveowners E34 Series Installation Guide TM Installation cont EQUIPMENT DAMAGE Do not use CTs with current mode outputs Failure to follow this instruction can r...

Page 14: ...able ties are included with the product for strain relief on the E34A28 and E34E28 Insert the strain relief device into one of the available holes on the adapter board Figure 7A Gather all current sen...

Page 15: ...f Treat all measurement circuits and CT connections as energized live Failure to follow these instructions will result in death or serious injury DANGER ESD SENSITIVE DEVICES Observe handling precauti...

Page 16: ...being monitored without exceeding the limit For higher voltages e g 480 V line to line this must be supplied from a source that is 277 Vac or less It could be a separate source or a transformer can be...

Page 17: ...Othercompanies trademarksareherebyacknowledgedtobelongtotheirrespectiveowners E34 Series Installation Guide TM Figure13 1 Connect 2 wire or 4 wire Modbus RS 485 daisy chain network Figures 14 and 15...

Page 18: ...rated for the installation HAZARD OF ELECTRIC SHOCK EXPLOSION OR ARC FLASH Turn off all power supplying equipment before working on or inside the equipment Use a properly rated voltage sensing device...

Page 19: ...etwork must have a unique address Set the switch block to assign a unique address before the device is connected to the Modbus RS 485 network If an address is selected that conflicts with another devi...

Page 20: ...heVeris V logoaretrademarksorregisteredtrademarksof VerisIndustries L L C intheUSAand orothercountries Othercompanies trademarksareherebyacknowledgedtobelongtotheirrespectiveowners E34 Series Installa...

Page 21: ...gisteredtrademarksof VerisIndustries L L C intheUSAand orothercountries Othercompanies trademarksareherebyacknowledgedtobelongtotheirrespectiveowners E34 Series Installation Guide TM DO NOT USE ZERO 1...

Page 22: ...lying equipment before working on or inside the equipment Product may use multiple voltage power sources Disconnect ALL sources before servicing Use a properly rated voltage sensing device to confirm...

Page 23: ...nd the E34E if they are not already connected Secure a ferrite filter included around the Ethernet cable to ensure the device meets emission requirements E34E 2 Temporarily change the IP address of th...

Page 24: ...ris V logoaretrademarksorregisteredtrademarksof VerisIndustries L L C intheUSAand orothercountries Othercompanies trademarksareherebyacknowledgedtobelongtotheirrespectiveowners E34 Series Installation...

Page 25: ...net mask Enterstatic IPaddress Entersubnet mask f Click OK 3 Open a PC web browser and enter the IP address of the E34E default address is 192 168 1 24 to access the GUI If this is the first time logg...

Page 26: ...et BBMD device d Click the Update IP Settings button The E34E changes its settings e Click the System Restart button and wait for the E34E to fully initialize The GUI will connect when the E34E is ins...

Page 27: ...tocols the product communicates with The E34E supports five protocols some of which can operate simultaneously The table below shows which protocols are supported in each mode Protocol Mode Primary Pr...

Page 28: ...e MAC address To use this product with MS TP the BACnet system must support the discovery and use of a BACnet router on the MS TP trunk and any devices beyond it This virtual router creates an exclusi...

Page 29: ...addresses on the MS TP network The final field for the BACnet MS TP mode is RTC_Control which selects which protocol BACnet or Modbus has write access to the RTC If 0 BACnet is selected the RTC is set...

Page 30: ...atever values are entered here must also be used in the MIB browser or SNMP access software to communicate with this device The Read_Community string is used to enable reading data The Write_Community...

Page 31: ...m 1 to 65534 if other values are entered the network number defaults to 5 b Device_ID Offset Every BACnet device must have a BACnet Device_ID number that is unique throughout the entire enterprise Sin...

Page 32: ...Data Sharing WriteProperty B DS WP B K 1 10 BIBB Data Sharing WritePropertyMultiple B DS WPM B K 1 12 BIBB Data Sharing COV B DS COV B K 2 2 BIBB Alarm and Event Notification Internal B AE N I B K 2...

Page 33: ...e Object_name property The E34E supports Subscribe_COV with default COV increment values assigned as shown in the data object tables If these values are not appropriate for a specific application writ...

Page 34: ...rs and to the data set under Modbus address 2 or BACnet device identified as Node_2 in the GUI For each panel data is arranged under six tree branches The Configuration branch contains all writable co...

Page 35: ...sswords to help prevent unauthorized access to device settings and information Disable unused ports services and default accounts where possible to minimize pathways for malicious attacks Place networ...

Page 36: ...control system provides the capability to Manage connections through managed interfaces consisting of appropriate boundary protection devices such as proxies gateways routers firewalls and encrypted...

Page 37: ...zation or contact your network administrator for example maximum password age or history policies DefaultPasswordandUserAccounts Accessing the GUI for the First Time with Firmware Version 1 027 or Hig...

Page 38: ...TLS certificate recommended and most secure mode Once this mode is selected the user can drag and drop their own SSL Certificate and Private Key files into their respective fields If the Private Key...

Page 39: ...rd tab Enter the new alphanumeric complex password in the Password and Confirm Password fields Click Confirm to save the changes To confirm the changes click the Logout button and access the GUI with...

Page 40: ...your network administrator to determine a responsible method of disposal Dispose the device according to the legislation of the country Some regulatory organizations include The United States Environm...

Page 41: ...ufficient biasing on the Modbus bus Modbus physical specification calls for 450 650 biasing This is usually provided by the master The main board has a slow flashing amber light E34A models One or mor...

Page 42: ...Guide TM China RoHS Compliance Information Environment Friendly Use Period EFUP Table SJ T11364 O GB T 26572 X GB T 26572 This table is made according to SJ T 11364 O indicates that the concentration...

Reviews: