E34 Series Installation Guide

TM

Safety Information

Control system design must consider the potential failure modes of control paths and, for certain critical control functions, provide a means to acheive a safe state 

during and after a path failure. Examples of critical control functions are emergency stop and over-travel stop.

For additional information about anticipated transmission delays or failures of the link, refer to NEMA ICS 1.1 (latest edition). 

Safety Guidelines for the 

Application, Installation, and Maintenance of Solid-State Controls

 or its equivalent in your specific country, language, and/or location.

LOSS OF CONTROL

•   Ensure that the system will reach a safe state during and after a control path failure.
•  Separate or redundant control paths must be provided for critical control functions.
•  Test the effect of transmission delays or failures of communication links.
•  Each implementation of equipment using communication links must be individually and thoroughly tested for proper operation before placing 

it in service.

Failure to follow these instructions can result in death or serious injury.

WARNING

Provide a disconnect device to disconnect the meter from the supply source. Place this device in close proximity to the equipment and within easy reach of the 
operator, and mark it as the disconnecting device. The disconnecting device shall meet the relevant requirements of IEC 60947-1 and IEC 60947-3 and shall be 
suitable for the application. In the US and Canada, disconnecting fuse holders can be used. Provide overcurrent protection and disconnecting device for supply 
conductors with approved current limiting devices suitable for protecting the wiring.

FCC PART 15 INFORMATION

E34A Models: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC rules. These limits 

are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses, and can radiate radio 
frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there 
is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, 
which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following 
measures:

 

– Reorient or relocate the receiving antenna.

 

– Increase the separation between the equipment and receiver.

 

– Connect the equipment to an outlet on a circuit different from that of the receiver.

 

– Consult the dealer or an experienced radio/TV technician for help.

The user is cautioned that any changes or modifications not expressly approved by Veris Industries could void the user’s authority to operate the equipment.

E34E Models:  This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits 

are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment 
generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful 
interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be 
required to correct the interference at his own expense.

CAN ICES-3 (B) /NMB-3(B) 

If this product is used in a manner not specified by the manufacturer, the protection provided by the product may be impaired.
The installer is responsible for conformance to all applicable codes.
The safety of any system incorporating this equipment is the responsibility of the assembler of the system.
Note: See IEC 60950-1:2005, Annex W for more information on communications and I/O wiring connected to multiple devices. 
Protective bonding: electrical connection of accessible conductive parts or protective screening to provide electrical continuity to the means 
for connection of an external protective conductor.

HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH

•  This product must be installed inside a suitable fire and electrical enclosure.
•  Follow safe electrical work practices. See NFPA 70E in the USA, or applicable local codes.
•  This equipment must only be installed and serviced by qualified electrical personnel.
•  Do not use this device for critical control or protection applications where human or equipment safety relies on the operation of the control 

circuit.

•  Do not install this product in hazardous or classified locations.
•  Read, understand and follow the instructions before installing this product.
•  Turn off all power supplying equipment before working on or inside the equipment.
•  Product may use multiple voltage/power sources. Disconnect all sources before servicing.
•  Use a properly rated voltage sensing device to confirm that power is off. 
•  Do not use data from this device to confirm power is off.
•  Replace all doors, covers and protective devices before powering the equipment.
•  Do not exceed the product's ratings or maximum limits.
•  Treat communications and I/O wiring connected to multiple devices as hazardous live until determined otherwise.

Failure to follow these instructions will result in death or serious injury.

DANGER

Summary of Contents for E34 Series

Page 1: ...ng an RS 485 Modbus protocol E34E models also incorporate Ethernet with support for BACNet IP Modbus TCP and SNMP protocols and include BACnet MS TP serial capability and a sturdy metal enclosure The...

Page 2: ...ference by one or more of the following measures Reorient or relocate the receiving antenna Increase the separation between the equipment and receiver Connect the equipment to an outlet on a circuit d...

Page 3: ...Rate DIP switch selectable 9600 19200 38400 Parity DIP switch selectable NONE ODD EVEN Communication Format 8 data bits 1 start bit 1 stop bit Termination 5 position plug in connector TX TX SHIELD TX...

Page 4: ...ons E34E Models FCC part 15 Class A EN6100 6 4 EN61326 1 Class A Conducted and Radiated Immunity EN 61000 6 2 and EN 61326 1 See Configuration section for details The E34 must be installed in an appro...

Page 5: ...wledgedtobelongtotheirrespectiveowners E34 Series Installation Guide TM Table of Contents Dimensions 6 Product Diagrams 7 Data Outputs 9 Blink Codes for Status LED 10 Installation 11 Wiring 15 Configu...

Page 6: ...emarksof VerisIndustries L L C intheUSAand orothercountries Othercompanies trademarksareherebyacknowledgedtobelongtotheirrespectiveowners E34 Series Installation Guide TM Dimensions E34ABaseBoard 7 3...

Page 7: ...L C intheUSAand orothercountries Othercompanies trademarksareherebyacknowledgedtobelongtotheirrespectiveowners E34 Series Installation Guide TM Product Diagrams Dimensions cont 28 MeterCTAdapterAssem...

Page 8: ...r 3 Control power fuse 600 Vac 500 mA time lag factory replaceable 4 Alive LED E34A models Red green amber LEDs Blink codes are described in the Blink Codes for Status LED section of this document 5 V...

Page 9: ...2 or 3 channels that are adjacent in the panel to a logical meter referred to in the point map as a logical circuit that provides accurate multi phase measurement totals Map these logical circuits by...

Page 10: ...ents Current multi phase average and per phase Current phase angle per branch Real power kW multi phase total and per phase Apparent power kVA multi phase total and per phase Power factor multi phase...

Page 11: ...ons Read understand and follow the instructions before installing this product Turn off all power supplying equipment before working on or inside the equipment Product may use multiple voltage power s...

Page 12: ...kets placed on the two sides for vertical mounting If desired you can move the brackets from the sides to the ends of the housing Loosen the screws on the sides of the E34 that hold the brackets in pl...

Page 13: ...eherebyacknowledgedtobelongtotheirrespectiveowners E34 Series Installation Guide TM Installation cont EQUIPMENT DAMAGE Do not use CTs with current mode outputs Failure to follow this instruction can r...

Page 14: ...able ties are included with the product for strain relief on the E34A28 and E34E28 Insert the strain relief device into one of the available holes on the adapter board Figure 7A Gather all current sen...

Page 15: ...f Treat all measurement circuits and CT connections as energized live Failure to follow these instructions will result in death or serious injury DANGER ESD SENSITIVE DEVICES Observe handling precauti...

Page 16: ...being monitored without exceeding the limit For higher voltages e g 480 V line to line this must be supplied from a source that is 277 Vac or less It could be a separate source or a transformer can be...

Page 17: ...Othercompanies trademarksareherebyacknowledgedtobelongtotheirrespectiveowners E34 Series Installation Guide TM Figure13 1 Connect 2 wire or 4 wire Modbus RS 485 daisy chain network Figures 14 and 15...

Page 18: ...rated for the installation HAZARD OF ELECTRIC SHOCK EXPLOSION OR ARC FLASH Turn off all power supplying equipment before working on or inside the equipment Use a properly rated voltage sensing device...

Page 19: ...etwork must have a unique address Set the switch block to assign a unique address before the device is connected to the Modbus RS 485 network If an address is selected that conflicts with another devi...

Page 20: ...heVeris V logoaretrademarksorregisteredtrademarksof VerisIndustries L L C intheUSAand orothercountries Othercompanies trademarksareherebyacknowledgedtobelongtotheirrespectiveowners E34 Series Installa...

Page 21: ...gisteredtrademarksof VerisIndustries L L C intheUSAand orothercountries Othercompanies trademarksareherebyacknowledgedtobelongtotheirrespectiveowners E34 Series Installation Guide TM DO NOT USE ZERO 1...

Page 22: ...lying equipment before working on or inside the equipment Product may use multiple voltage power sources Disconnect ALL sources before servicing Use a properly rated voltage sensing device to confirm...

Page 23: ...nd the E34E if they are not already connected Secure a ferrite filter included around the Ethernet cable to ensure the device meets emission requirements E34E 2 Temporarily change the IP address of th...

Page 24: ...ris V logoaretrademarksorregisteredtrademarksof VerisIndustries L L C intheUSAand orothercountries Othercompanies trademarksareherebyacknowledgedtobelongtotheirrespectiveowners E34 Series Installation...

Page 25: ...net mask Enterstatic IPaddress Entersubnet mask f Click OK 3 Open a PC web browser and enter the IP address of the E34E default address is 192 168 1 24 to access the GUI If this is the first time logg...

Page 26: ...et BBMD device d Click the Update IP Settings button The E34E changes its settings e Click the System Restart button and wait for the E34E to fully initialize The GUI will connect when the E34E is ins...

Page 27: ...tocols the product communicates with The E34E supports five protocols some of which can operate simultaneously The table below shows which protocols are supported in each mode Protocol Mode Primary Pr...

Page 28: ...e MAC address To use this product with MS TP the BACnet system must support the discovery and use of a BACnet router on the MS TP trunk and any devices beyond it This virtual router creates an exclusi...

Page 29: ...addresses on the MS TP network The final field for the BACnet MS TP mode is RTC_Control which selects which protocol BACnet or Modbus has write access to the RTC If 0 BACnet is selected the RTC is set...

Page 30: ...atever values are entered here must also be used in the MIB browser or SNMP access software to communicate with this device The Read_Community string is used to enable reading data The Write_Community...

Page 31: ...m 1 to 65534 if other values are entered the network number defaults to 5 b Device_ID Offset Every BACnet device must have a BACnet Device_ID number that is unique throughout the entire enterprise Sin...

Page 32: ...Data Sharing WriteProperty B DS WP B K 1 10 BIBB Data Sharing WritePropertyMultiple B DS WPM B K 1 12 BIBB Data Sharing COV B DS COV B K 2 2 BIBB Alarm and Event Notification Internal B AE N I B K 2...

Page 33: ...e Object_name property The E34E supports Subscribe_COV with default COV increment values assigned as shown in the data object tables If these values are not appropriate for a specific application writ...

Page 34: ...rs and to the data set under Modbus address 2 or BACnet device identified as Node_2 in the GUI For each panel data is arranged under six tree branches The Configuration branch contains all writable co...

Page 35: ...sswords to help prevent unauthorized access to device settings and information Disable unused ports services and default accounts where possible to minimize pathways for malicious attacks Place networ...

Page 36: ...control system provides the capability to Manage connections through managed interfaces consisting of appropriate boundary protection devices such as proxies gateways routers firewalls and encrypted...

Page 37: ...zation or contact your network administrator for example maximum password age or history policies DefaultPasswordandUserAccounts Accessing the GUI for the First Time with Firmware Version 1 027 or Hig...

Page 38: ...TLS certificate recommended and most secure mode Once this mode is selected the user can drag and drop their own SSL Certificate and Private Key files into their respective fields If the Private Key...

Page 39: ...rd tab Enter the new alphanumeric complex password in the Password and Confirm Password fields Click Confirm to save the changes To confirm the changes click the Logout button and access the GUI with...

Page 40: ...your network administrator to determine a responsible method of disposal Dispose the device according to the legislation of the country Some regulatory organizations include The United States Environm...

Page 41: ...ufficient biasing on the Modbus bus Modbus physical specification calls for 450 650 biasing This is usually provided by the master The main board has a slow flashing amber light E34A models One or mor...