Installation Guide
Power Monitoring
E31E Series
TM
Installation
Observe precautions for handling static sensitive
devices to avoid damage to the circuitry that
is not covered under the factory warranty.
Disconnect power to the panel before beginning the installation.
1. Locate a surface inside the electrical enclosure to mount the E31E. Decide whether to mount the E31E vertically or horizontally.
The E31E is shipped with the brackets placed for vertical mounting. If mounting horizontally, loosen the screws on the sides of
the E31E that hold the brackets in place (do not fully remove the screws from the E31E housing). Loosen the screws on the other
two sides of the housing (do not fully remove the screws from the E31E housing), and set the brackets into their new positions.
Tighten all screws.
Vertical Mounting Horizontal Mounting
2. Install the E31E in the panel (hardware not provided). A grounding connection is located on the housing (see below). Use this
stud to ground the device when it is mounted on a nonconductive surface.
CURRENT SENSOR STRIP
CURRENT SENSOR STRIP
CURRENT SENSOR STRIP
CURRENT SENSOR STRIP
Panel 2
Panel 1
E31E
Ground
Split-Core Current
Sensors
50 A Split-Core CT
100 A Split-Core CT
200 A Split-Core CT
Voltage Rating 300 VAC
300 VAC (CE), 600 VAC (UL)
300 VAC (CE), 600 VAC (UL)
Accuracy
±1%
±0.5%
±1%
Temperature
0° to 60°C
0° to 60°C
0° to 60°C
Agency
UL 61010-1 Recognized, EN61010-1 UL 61010-1 Recognized, EN61010-1 UL 61010-1 Recognized, EN61010-1