background image

PV500-27A  07/04 

2

VENTURA

®

 

LOW NOx WATER HEATER

 

 

START-UP PROCEDURES

 

 

CAUTION: DO NOT RELIGHT PILOT OR START BURNER WITH COMBUSTION 
CHAMBER FULL OF GAS VAPOR, OR WITH VERY HOT COMBUSTION CHAMBER. 

 
 

1. Study the Installation & Maintenance 

manual for the burner carefully.  

 
2.  Fill the water heater tank with water. 

Open the relief valve or a nearby hot 
water faucet to allow air in the tank to 
escape. Be sure all connections into the 
tank are tight, as leaks at tank fittings will 
damage the insulation. 

 
3.  Follow the enclosed warnings on the 

water temperature control when setting 
the   operating  thermostats.   The  water  

 

 
 

heater has three temperature controls. 
The top control is the temperature limiting 
device and should be set at 200°F. The 
lowest control is the operating thermostat 
and must be adjusted 10 degrees (10°) 
lower then the upper operating control. A 
common setting is 130°F for the upper 
operating control and 120°F for the 
operating thermostat. Your thermostat 
settings must take into account your 
application. To avoid scalds, follow the 
enclosed warnings on water temperature 
control when setting the thermostats. 

 

 

 
 
CAUTION: ON MODELS WITH FLUE GAS RECIRCULATION (FGR), THE FGR DUCT 
AND PLUMBING WILL BE HOT DURING AND AFTER OPERATION. USE CARE TO 
AVOID CONTACT WITH SKIN WHILE MAKING ADJUSTMENTS. 
 
 

 
CAUTION: CONDUCT THE FOLLOWING GAS TRAIN LEAKAGE TEST BEFORE 
START-UP, ANNUAL INTERVALS AND PRIOR TO INVESTIGATING THE 
CAUSE OF ANY REPORTED OCCURRENCES OF DELAYED IGNITION. 

 

 

1.  Using an appropriate bubble detection 

solution, thoroughly coat all gas train pipe 
connections. If any bubbles are detected, 
the leaking connection must be tightened, 
recoated and rechecked to assure 
stoppage of the leak. 

 
2.  Attach a manometer, to measure gas 

pressure, at the manual gas shutoff valve 
located just upstream of the gas train. 
Adjust gas train inlet pressure to the 
specified value on heater decal and tightly 
close the gas train manual shutoff valve 
closest to burner. 

 
 

3.  Reattach the manometer to the gas train 

manual shutoff valve at the burner and 
record the measured gas pressure in 
inches of water column (in W.C.). 
Measure gas pressure again after 15 
minutes. If gas pressure has increased 
0.5" W.C. or more, the gas leak must be 
isolated to one or more of the operating 
gas valves; for example, a solenoid 
actuated gas shutoff valve. After any 
leaking valve is replaced, the 
reassembled gas train must be leak 
tested again before start-up is attempted. 

(NOTE: All gas valves removed 
because of suspected leakage must be 
returned to PVI Customer Service for 
disposition.)

 

Reviews: