MOUNTING AND SET-UP
MINIMUM DISTANCE FOR ACCESSING THE UNIT
While mounting the unit provide enough space for its maintenance or repair work.
A
- distance required for water
heater connection. The distance is se-
lected depending on the installation
conditions at the discretion of the in-
staller.
min 20мм
min B
A
Model
VUT 600 P
W EC
VUT 1000 P
W EC
min B, mm
850
800
UNIT MOUNTING
The unit must be suspended to the ceiling on the threaded rod that is fixed inside a dowel.
Washer
Nut
Vibration-damping
rubber
Nut and
lock-nut
Example
To attain the best performance of the unit and to minimise turbulence-induced air pressure losses connect a straight air duct section on
both sides of the unit while mounting.
Minimum straight air duct length:
•
equal to 1 air duct diameter on intake side.
•
equal to 3 air duct diameters on outlet side.
If the air ducts are too short or not connected, protect the unit parts from ingress of foreign objects, e.g. by covering the spigots with a
protecting grille or other protecting device with mesh width not more than 12.5 mm to prevent uncontrollable access to the fans.