7.1.17
Test Status
This indicates ON if battery test is currently running, otherwise OFF.
7.1.18
UPS Mode
This indicates UPS mode has been enabled.
If enabled systems transfer to battery automatically in the event of Supply loss.
7.1.19
UPS Mode Status
This indicates if the system is running from battery due to Supply loss.
7.2
Battery Status Page
7.2.1
Capacity Test Settings Results
This field displays the time stamp for the last battery capacity test was performed, the
average load current, and the average enclosure temperature the test was performed
at.
7.2.2
Current Status
This field displays the estimated time to perform the battery capacity test. The test is
terminated when the battery voltage goes below 11 Vdc for a 12 Vdc system or 22 Vdc
for a 24 Vdc system. This is based on the battery capacity curves for lead acid batteries
and the average load current of the system. The field also displays the minimum run
time for the battery capacity test and the status of the last test performed.