12.3.10
Events
When Events are generated, they are reported via unsolicited messaging (if enabled),
or queue to the event list for reading when polling for Class 2 data, or reading Binary
events. Event points correspond to Binary Input Points.
Point
Description
State
Value
1
Low Battery Capacity Event
Tripped Event
0x81
2
Low Battery Voltage Event
Tripped Event
0x81
4
Aux IO Channel 1 Event
Tripped Event
0x81
5
Aux IO Channel 2 Digital In
Tripped Event
0x82
13. Modbus Protocols
Overview
MODBUS® Protocol, a messaging structure developed by Modicon in 1979, using a Master Slave
approach. It is one of the simplest and widely adopted instrument automation protocols. Complete
protocol details can be found at
www.modbus.org
BTRM supports Modbus overRS232 Serial and TCP/IP for
To configure the Modbus protocol please see section 7.9 for further details
Modbus Point Reference List Spreadsheet
Click on list below for Excel Spreadsheet version of the Modbus Point List
13.1
Function 01 Boolean (Coils) | Read Discrete Inputs
BTRM Modbus Points Listing V2020-04-20.zip
Point Description
State
Value
State
Value
0
Battery Data Reset
Session has Data
0x01
Data Empty
0x00
1
Battery LVD Status
LVD is enabled
0x01
LVD disabled
0x00
2
Battery Test Enable
Test is enabled
0x01
Test is disabled
0x00
3
Battery Start Test
Test running
0x01
Test not running
0x00