Vent-Axia Lo-Carbon Revive Installation And Wiring Instructions Download Page 4

3. 

Loosen the screw at the bottom of the grille, and then remove the grille by 
carefully pulling away from the housing.   

4. 

Mark the screw centres through the holes in the fan back plate. Drill, plug 
and screw into position.  

5. 

Wire the fan as described in Section B-Wiring. Adjust any settings as 
required (see Section C-Setup). 

6. 

After installation, ensure impeller rotates freely. 

7. 

Replace the grille and tighten the retaining screw.  

 

 

WINDOW MOUNTING 

For window mounting refer to the instructions provided with the kit. 
 

B. WIRING.

 

WARNING: THE FAN AND ANCILLARY CONTROL EQUIPMENT 
MUST BE ISOLATED FROM THE POWER SUPPLY DURING 
INSTALLATION OR MAINTENANCE. 
 

IMPORTANT 

  The cross - sectional area of supply cord used should be ranged from 1 -1.5mm

2

  The  extraction  fan  or  transformer  (SELV  models)  is  suitable  for  connection  to 

220-240V 50Hz supply. 

 

The

 

Transformer (SELV models only)

 

MUST

 be surface mounted to allow air 

to freely circulate around the unit. When installed in a loft void it 

MUST

 

NOT

 be 

enclosed or covered with insulation.

 

  The fan is a class ll double insulated product and 

MUST NOT 

be earthed. 

 

1. 

Select and follow the appropriate wiring diagram. (Fig. 1, 2, 3, OR 4, 5, 6) 

2. 

Check all connections have been made correctly and ensure all terminal 
connections and supply wires are securely fastened. 

3. 

Ensure the impeller rotates and is free from obstructions. 

 

C. SETUP 
Accessing the commissioning menu 

To configure the fan first remove the grille. With the grille removed the control board is 
visible (Fig.7). Do NOT isolate the fan from the power 
supply  as  configuration  requires  power  to  the  fan; 
removing  the  grille  will  automatically  stop  the  impeller 
from spinning

.  

 

Once the fan has been commissioned please write the 
installation date in the box on the label provided. 

 
 
 

IMPORTANT 

Do  NOT

  attempt  to  remove  the  circuit  board  cover  (Fig.7).  This 

covers  the  high  voltage  power  supply,  preventing  the  risk  of  an 
electric shock.   

 

 

Summary of Contents for Lo-Carbon Revive

Page 1: ...N Revive 7 473848 Revive 7 SELV 473849 Revive 5 473850 Revive 5 SELV 473851 Revive 473852 Revive SELV 473853 Revive Intermittent 478367 Revive SELV 478368 Intermittent PLEASE READ INSTRUCTIONS IN CONJ...

Page 2: ...cting all poles having a contact separation of at least 3mm C Ensure that the mains supply Voltage Frequency and Phase complies with the rating label D The Fan should only be used in conjunction with...

Page 3: ...NSFORMER SELV Models only 1 The transformer must not be installed in a shower cubicle or enclosure It must be sited away from direct sources of water spray and out of reach 1 5m of a person using a fi...

Page 4: ...dels only MUST be surface mounted to allow air to freely circulate around the unit When installed in a loft void it MUST NOT be enclosed or covered with insulation The fan is a class ll double insulat...

Page 5: ...ion type settings kitchen or bathroom and ducted or window wall The difference between bathroom and kitchen mode is shown above the boost speeds are higher for kitchen applications If the fan is insta...

Page 6: ...usted after commissioning as a pass code is required to access the menu This can be set in the menu to any 3 digit hexadecimal combination If the lock feature is enabled when a button is pressed the d...

Page 7: ...to move the display to the next data set Data Logger Menu When the display is rotated the decimal point will no longer display eg 055 represents 5 5KWh Data Examples Text scrolling from right to left...

Page 8: ...orated it could take up to 2 weeks for the humidity levels to stabilise Please leave the fan to dry out the room and after this period the fan should run normally ii The humidity set point could be se...

Page 9: ...1 with no trickle facility The fan is internally fused Fig 3 Continuous trickle with boost facility The fan is internally fused Fig 1 Continuous trickle with boost via pull cord The fan is internally...

Page 10: ...els Fig 6 Continuous trickle with boost facility via LS or internal pullcord SELV models Fig 4 Continuous trickle with pullcord boost SELV models N L 1 Phase Supply 220 240V 50Hz FUSE Switched Fused S...

Page 11: ...the screw at the bottom of the grille 2 Pull the grille clear of the screw and lift away Circuit board cover DO NOT REMOVE Control Board Display INCREASE Value REDUCE Value MODE Button Note Revive 7...

Page 12: ...to misuse neglect or damage Has not been modified or repaired by any person not authorised by the company IF CLAIMING UNDER TERMS OF GUARANTEE Please return the complete product carriage paid to your...

Reviews: