Vent-Axia INTEGRA PLUS Installation And Wiring Instructions Download Page 2

 

Page 2 of 12

  VENT-AXIA INTEGRA PLUS – HEAT RECOVERY VENTILATION UNIT 

 INSTALLATION AND MAINTENANCE INSTRUCTIONS 

 

Read the following instructions in conjunction with the illustrations before commencing installation.

 

 

Product Description 

 
The INTEGRA PLUS is a loft/ceiling mounted heat recovery ventilation unit for domestic and commercial 
applications. It is designed for connection to 150mm-diameter insulated flexible or rigid ventilation ducting. 
The unit’s two fans and heat exchanger arrangement simultaneously supply and extract air while transferring heat 
from the stale exhaust airflow to the fresh intake airflow. This provides up to 70% heat recovery from the stale 
extracted air.  
Separation of the exhaust airflow and intake airflow is maintained throughout the unit. 
The fan motors have maintenance free self lubricating long life bearings and are fitted with thermal overload 
protection, which in the event of a fault causing a motor to overheat will cut off the electrical supply to that motor. 
The electrical power consumption of the unit is 425W when running at maximum speed from a 230V supply. 

 

 
 

SAFETY - IMPORTANT POINTS TO NOTE 

 

1.  THIS APPLIANCE IS INTENDED FOR PERMANENT CONNECTION TO THE MAINS ELECTRICAL SUPPLY FIXED WIRING AND 

MUST BE INSTALLED BY A SUITABLY QUALIFIED PERSON. 

2.   THIS APPLIANCE MUST BE SITED AND CONNECTED IN ACCORDANCE WITH CURRENT UK BUILDING, FACTORY AND IEE 

WIRING REGULATIONS (BS7671) OR THE APPROPRIATE NATIONAL REGULATIONS IN YOUR COUNTRY. 

3.  WIRING TO THE APPLIANCE IN THE UK MUST BE VIA A FUSED AND SWITCHED CONNECTION UNIT INCORPORATING A 

DOUBLE POLE SWITCH WITH 3mm CONTACT SEPARATION AND CONFORMING TO BS5733 OR BS1363 PART 4.  A 3 AMP 
BS1362 FUSE SHOULD BE FITTED TO THE CONNECTION UNIT, WHICH MUST BE LOCATED OUTSIDE OF A ROOM 
CONTAINING A FIXED BATH OR SHOWER. 

4.   WARNING:  THIS APPLIANCE IS CLASS I AND IT MUST THEREFORE BE EARTHED. 
5.  CHECK THE RATING LABEL ON THE APPLIANCE TO ENSURE THAT THE ELECTRICAL SUPPLY IS COMPATIBLE WITH THE 

APPLIANCE WHICH IS RATED AT 230V AC 50 Hz. 

6.  THIS APPLIANCE MUST BE SITED OUT OF REACH OF ANY PERSON USING A FIXED BATH OR SHOWER. 
7.  IN SITUATIONS WHERE MOISTURE CAN BE PRESENT IN THE AIR, THE APPLIANCE SHOULD BE CONNECTED TO A 

CONDENSATE DRAINAGE SYSTEM. 

8.  IN ENVIRONMENTS WHERE PARTICLE LADEN AIR IS BEING EXTRACTED PROVISION MUST BE MADE FOR ADEQUATE 

FILTRATION BEARING IN MIND SYSTEM RESISTANCE AND REGULAR FILTER MAINTENANCE. 

9.  THIS APPLIANCE MUST BE SITED AWAY FROM DIRECT SOURCES OF HEAT IN EXCESS OF 40 DEGREES C. 
10. SITE THE APPLIANCE AND ARRANGE THE ASSOCIATED DUCTING AND GRILLES TO PROVIDE A BALANCED CIRCULATION 

OF AIR. 

11. THE EXTERNAL INTAKE TERMINALS ASSOCIATED WITH THIS APPLIANCE MUST BE SITED AT LEAST 1000mm AWAY FROM 

THE FLUE OF A FUEL BURNING APPLIANCE/ OTHER EXTERNAL GRILLE TO PREVENT THE BACKFLOW OF GASES. 

12. THIS APPLIANCE IS NOT INTENDED FOR USE BY PERSONS (INCLUDING CHILDREN) WITH REDUCED PHYSICAL, SENSORY 

OR MENTAL CAPABILITIES, OR LACK OF KNOWLEDGE, UNLESS THEY HAVE BEEN GIVEN SUPERVISION OR INSTRUCTION 
CONCERNING USE OF THE APPLIANCE BY A PERSON RESPONSIBLE FOR THEIR SAFETY. 

13. CHILDREN SHOULD BE SUPERVISED TO ENSURE THAT THEY DO NOT PLAY WITH THE APPLIANCE. 
14. ALL SAFETY REGULATIONS AND REQUIREMENTS MUST BE STRICTLY FOLLOWED TO PREVENT HAZARDS TO LIFE AND 

PROPERTY BOTH DURING AND AFTER INSTALLATION AND DURING ANY SUBSEQUENT MAINTENANCE AND SERVICING. 

15. SWITCH OFF THE MAINS ELECTRICAL SUPPLY BEFORE COMMENCING INSTALLATION, MAINTENANCE OR SERVICING. 
 

 
 
 
 
 

Summary of Contents for INTEGRA PLUS

Page 1: ...INTEGRA PLUS Installation and Wiring Instructions 230V 50Hz PLEASE READ INSTRUCTIONS IN CONJUNCTION WITH ILLUSTRATIONS PLEASE SAVE THESE INSTRUCTIONS IPX2 Stock Ref N INTEGRA PLUS 437666...

Page 2: ...NFORMING TO BS5733 OR BS1363 PART 4 A 3 AMP BS1362 FUSE SHOULD BE FITTED TO THE CONNECTION UNIT WHICH MUST BE LOCATED OUTSIDE OF A ROOM CONTAINING A FIXED BATH OR SHOWER 4 WARNING THIS APPLIANCE IS CL...

Page 3: ...Page 3 of 12 Cover Heat Recovery Cell Supply Motor Base Extract Motor Controller Air Direction Exploded View of Fan unit Supply to Rooms Extract from Rooms Intake from Outside Exhaust to Outside...

Page 4: ...here are two forms of installation for the INTEGRA PLUS To mount the unit on joists Place the unit across two beams and attach the appropriate cabling drainage and ductwork to the unit with the Vent A...

Page 5: ...DS THE CONDENSATE DRAIN Fig 3a Mounted on joists Fig 3b Ceiling mounted 8 CORE CONTROLLER CABLE 8 CORE CONTROLLER CABLE Fig 4 Water trap details WATER TRAP CONDENSATION DRAIN FROM UNIT SILICON SEALER...

Page 6: ...suitable installation site allow for an extra 30mm clearance either end for cable glands Note that the unit can be ceiling or floor mounted The site selected must allow sufficient space around the uni...

Page 7: ...he appropriate terminals 5 Ensure the wires are securely fixed into the terminal block after use 6 A 10 12mm outside diameter 3 core mains lead should enter the controller hosing via the cable gland n...

Page 8: ...otor connections should be fitted through the cable entry on the left while the cable entry on the right should be used for switches 10 The cable gland around this cable must also be securely fitted 1...

Page 9: ...Wiring via 3 Ambient Response Humidity Sensors Normal Purge Fig 4 Wiring via an Ambient Response Humidity Sensor Timeswitch Boost Relay Com NC NO Fuse L N E 1 Phase supply 220 240V 50 Hz Switched fuse...

Page 10: ...m available Chlorine solution Cleaning Procedure 1 Heat Recovery Cell Remove from appliance and wash ensuring that the sterilising solution penetrates between the Cell plates All parts should be well...

Page 11: ...e end user Appendix 1 Air Performance Graph HR300XL Air Performance Extract Supply 0 100 200 300 400 500 600 0 100 200 300 400 500 600 Volume Pressure Pa m h l s 0 25 50 75 100 125 150 50V 62V 74V 86V...

Page 12: ...product will be repaired or at the Company s option replaced without charge provided that the product Has been installed and used in accordance with the instructions given with each unit Has not been...

Reviews: