26
Humidity Output Polarity*
(Setup Step 68)
Open (Normally Open)
means no voltage is sent to the
HUM
output when there is no
demand for humidity.
Closed (Normally Closed)
means voltage is sent to the
HUM
output when there is no
demand for humidity.
Dehumidify Output Polarity*
(Setup Step 69)
Open (Normally Open)
means no voltage is sent to the
DEHUM
output when there is no
demand to dehumidify.
Closed (Normally Closed)
means voltage is sent to the
DEHUM
output when there is
no demand to dehumidify.
Dehumidify Only With Cooling
(Setup Step 70)
When set to ON, Dehumidify will only turn on with a 1st stage cooling demand.
When set to OFF, Dehumidify will turn on at any time that the room humidity exceeds
the dehumidification setpoint.
Press the SETUP button, then press MODE repeatedly until the
desired setup step appears. Use the WARMER or COOLER buttons
to make selection. Press MODE to advance to the next step.
Press/hold MODE to go backwards to prior steps. Press SETUP to
leave the setup screens.
WARMER
COOLER
MODE
SETUP
Setup Steps