S T / V T V E N D O R
•
3 5 6 8 3 5 6 7 3 5 6 6 3 5 6 5
•
23
4 2 2 0 5 5 7 R e v A
NOTE
:
The sealed hermetic system should not be worked on outside the Factory Service Center
.
REFRIGERATION TROUBLESHOOTING
COMPRESSOR WILL NOT START
Problem
Possible Causes/Actions
1.
Vendor not plugged in.
2.
Tripped breaker or blown fuse.
3.
Faulty wall outlet
4.
Faulty (short or open) power cord.
Check power cord with a Multi-Meter.
5.
Improper wiring.
6.
Low voltage
Check the power source with a volt meter. Minimum of 103VAC for 115VAC, 60HZ,
Minimum of 195VAC for 230VAC, 50Hz.
7.
Overload defective
Overload is tripping to fast.
Check overload with a Multi-Meter.
8.
Start relay defective
Check start relay with a Multi-Meter.
9.
Compressor has open windings
Check compressor windings with a Multi-Meter.
10.
Defective refrigeration relay
Switch the controller to
Service Mode
then verify that the relay turns on by
using the
Test Relay
menu.
With refrigeration relay turned on in the
Test Relay
menu. Check relay
terminals 1 to 0 for 24VDC with a Multi-Meter. If power is present relay is bad.
11.
Defective control circuit
Unplug power to the vendor. Open the power panel. Use insulated jumper wires to
short the wire terminals on
Relay 1
; between 2 and 4 and between 6 and 8. Restore
power to the vendor. The compressor should start. If it does there is a problem in
the control circuit.
12.
Defective door switch
Check for proper door switch operation.
COMPRESSOR TRIPS ON OVERLOAD
1.
Improper voltage
Check voltage for 5-10% above or 5% below machines rated voltage. Check power
source with a Multi-Meter.
2.
Overload defective
Overload tripping to vast.
Check overload with a Multi-Meter.
3.
Relay defective
Relay Won’t open after starting.
Check relay with a Multi-Meter.
4.
Compressor has shorted winding
Check compressor windings with a Multi-Meter.
NOISY OR VIBRATING UNIT
1.
Components rubbing or touching
each other
Check fan blades and motor.
Loose shrouds and harness.
Copper tubing rubbing.
Loose or unsecured parts.
Dirty condenser fan blades.
2.
Worn or aged grommets
Check grommets.
3.
Compressor
Bad valves.
Slugging.
Bad windings (see Figure 21. Compressor Schematic).
Low voltage.
UNIT SHORT CYCLES
1.
Defective overload
Check overload with a Multi-Meter.
2.
Faulty condenser fan
3.
Airflow restricted
Dirty or blocked condenser coils
Dirty or blocked air filter
Dirty or blocked inlet or outlet screens