Velux KFC 100J Instructions Manual Download Page 3

3   VELUX

®

 IMPORTANT INFORMATION

Read instructions carefully before installation and operation. Keep instructions for future reference and hand them over to 

any new user.

Safety

• Installation must be carried out by a certified person in accordance with current national regulations.
•  To ensure correct operation and to avoid any damage or hazards, the installation and settings must be 

carried out carefully in accordance with these instructions.

• Check the technical data on the data plate. The data plate is placed in the control unit.
•  The installer must instruct the owner in the function of the control system including resetting of 

alarms and position of data plate and instructions.

•  Control unit for smoke exhaust KFC 100J must only be used by trained, competent and qualified per-

sonnel.

•  

WARNING!

 Make sure to use ESD protection when touching the printed circuit board for example 

during installation and service.

•  When resetting alarms, be sure not to touch conductive parts and make sure that no body parts can 

get caught in the staircase smoke exhaust when reactivated.

Product

•   The control unit is designed for the automatic opening of VELUX staircase smoke exhausts without or with exit CSJ 1210 

and CSJ 1211 respectively. Check whether the system complies with the applicable regulations. Connection to other prod-

ucts may cause damage or malfunction.

•  The control unit conforms with the EMC Directive for use in household, trade, industry and light industry.
•  When installed, the control unit complies with protection degree IP 30.
•  The packaging must be disposed of in accordance with national regulations.
•   The product, including batteries if any, is regarded as electrical and electronic equipment and contains hazardous materi-

als, components and substances. The crossed out wheeled bin symbolises that electrical and electronic equipment waste 

must not be disposed of together with household waste. It must be collected separately at recycling stations or other 

collection sites or retrieved directly from households to increase the possibilities of recycling, reuse and utilisation of elec-

trical and electronic equipment waste. By sorting electrical and electronic equipment waste with this symbol, you con-

tribute to reducing the volume of incinerated or buried waste and to reducing any negative impact on human health and 

the environment. Further information can be obtained from the local municipality's technical administration or from your 

VELUX sales company.

•  If batteries can be removed, product and batteries must be disposed of separately.
•   If the staircase smoke exhaust is exposed to high wind loads, it is recommended to connect the control unit to a wind 

sensor that automatically closes the staircase smoke exhaust.

Installation

•   The control unit must be connected directly to the mains supply in accordance with national regulations. Ensure that the 

mains supply cannot be disconnected unintentionally. It is recommended that disconnection is only possible using the 

mains switch or a key switch. At least one of these means for disconnection must be incorporated in the fixed wiring in 

accordance with national wiring requirements.

•  Protect the 230 V AC mains connection cable separately on site. 
•  Cable types, lengths and cross-sections must be in accordance with the technical specifications. 
•  All low-voltage cables (24 V DC) must be routed separately from the high-voltage cables.

Maintenance and service

•   Disconnect mains supply and back-up batteries before carrying out any maintenance or service work to the control unit 

and ensure that they cannot be reconnected unintentionally.

•   The control unit must be tested after installation, service work and alterations to the system. It must be inspected by quali-

fied personnel at least once a year. Tests and inspections must be documented in accordance with national regulations. 

•  Use only original spare parts. 
•  At the yearly inspection, the connected products must be checked according to their instructions.
•   The printed circuit board monitors the time between inspection periods. If more than 15 months have passed since the 

last inspection, the yellow light-emitting diode is on and an acoustic alarm sound.

•   The batteries must be checked at the yearly inspection. We recommend that the batteries are replaced at least every four 

years.

•  If you have any technical questions, please contact your VELUX sales company, see telephone list or www.velux.com.

Summary of Contents for KFC 100J

Page 1: ...r VELUX Steuereinheit f r Rauchabzug KFC 100J ENGLISH Instructions for VELUX control unit for smoke exhaust KFC 100J 061 0 6 795 176 6 9 4 8 3 4 60 4 9 1 061 D1 4 3 59D5 F 1 42E38 538 9 6 0 6 1 6 6 6...

Page 2: ...D5 75 59 D175 59D5 125 S 75 D125 5 59D5 5B 125 E 7C 1 59D5 C38 ECC 1 D1 41B4 59D5 C38 ECC 1 6UB 59D5 1D9 5 U25BC938D 59D5 Contents Cover sheet Contents Page 2 Important information Page 3 Functionalit...

Page 3: ...lectronic equipment waste By sorting electrical and electronic equipment waste with this symbol you con tribute to reducing the volume of incinerated or buried waste and to reducing any negative impac...

Page 4: ...s Once the staircase smoke exhaust has been closed the comfort ventilation functions are operational again After an alarm via an automatic detector blow out smoke or replace the detector before resett...

Page 5: ...ditional modules optional Transmitting alarms and or error indications An alarm or an error indication can be transmitted potential free by inserting the alarm error indication module Multi error indi...

Page 6: ...exhaust as long as the button on the ventilation switch is pressed and held dead man button SW 2 2 OFF Motors OPEN the staircase smoke exhaust once the ventilation switch is pressed Factory setting E...

Page 7: ...a potential free fire alarm system contact at the smoke detector input fire alarm module insertion 8 24 V 100 mA on extra terminal Warning No 72 hour emergency power supply when in use Further techni...

Page 8: ...5 D 95 1CD5B 9 59 5B T85 F 31 L U25B D95B5 General information Installation General information The back up batteries must be replaced every four years Retriggering the motors During the first 30 minu...

Page 9: ...current of the control unit 4 8 A Maximum cable length always routed from the control unit to the last junction box Operation current Sum of all motor currents per group Cross section 3 x 1 5 mm 5 x...

Page 10: ...Ventilation switches see cable length table Option transmission of wind rain alarm Option transmission of fire alarm Option transmission of multi error Option BUS 2 x 2 x O 8 mm or 5 x 1 5 mm 2 see c...

Page 11: ...break glass point CLOSE CLOSE CLOSE Indicator OPEN Alarm Alarm Motor term module Only insert terminal mod ule in the last or only detector Only insert the motor ter minal module in the last or only mo...

Page 12: ...e inserted in the last or only break glass point CLOSE CLOSE CLOSE Indicator OPEN Alarm Alarm Motor term module Only insert the motor ter minal module in the last or only motor Note If motors operate...

Page 13: ...9 4 D538 9C385 N 45BE 75 F B2581 D5 Mains Mains Mains fuse 1 A slow Motor Smoke detector Temperature fuse 72 C Module 1 Module 3 Module 2 Motor fuse 5 A slow Operation Battery Motor Break glass point...

Page 14: ...control unit is connected to VELUX staircase smoke exhaust CSJ 1210 or VELUX stair case smoke exhaust exit CSJ 1211 the total system is to be considered as a machine which is not to be put into servi...

Page 15: ...75 59 D175 59D5 125 S 75 D125 5 59D5 5B 125 E 7C 1 59D5 C38 ECC 1 D1 41B4 59D5 C38 ECC 1 6UB 59D5 1D9 5 U25BC938D 59D5 Inhaltsverzeichnis Deckblatt Inhaltsverzeichnis Seite 15 Wichtige Informationen S...

Page 16: ...ist nach nationalen Bestimmungen zu entsorgen Das Produkt einschlie lich eventuell vorhandener Batterien Akkus wird als ein Elektro und Elektronikger t betrachtet und enth lt gef hrliche Materialien...

Page 17: ...geltenden Vorschriften zu belegen Es sind nur Originalersatzteile zu verwenden Bei der j hrlichen Wartung m ssen die angeschlossenen Produkte gem ihren Anleitungen gepr ft werden Die Leiterplatte berw...

Page 18: ...r Rauchableitung sind die L ftungsfunktionen wieder in Betrieb Nach Ausl sung durch einen auto matischen Melder den Melder vor der R ckstellung ausblasen bzw erneuern Anzeige Die rote Alarm LED in der...

Page 19: ...ch Aufstecken des Alarm St rungsmoduls potentialfrei weitergeleitet werden Sammelst rung 1 x Wechslerkontakt max 60 V 1 A mit 3 poliger Anschlussklemme zur potentialfreien Weiterleitung an GLT usw Ala...

Page 20: ...d nur ber LEDs angezeigt Werkseinstellung SW 2 2 ON Antriebe fahren nur solange AUF wie der L ftungstaster bet tigt wird Totmann SW 2 2 OFF Antriebe fahren AUF sobald der L ftungstaster bet tigt wird...

Page 21: ...t 7 Ansteuerung durch potentialfreien BMA Kontakt am Rauchmeldereingang BMA Modul einsetzen 8 24 V 100 mA auf extra Klemme Achtung Bei Benutzung keine 72 Stunden Notstrom Weitere technische Daten Nenn...

Page 22: ...85 G95 9 C 9 9 4 41B75CD5 D 95 1CD5B 9 59 5B T85 F 31 L U25B D95B5 Allgemein Montage Allgemein Die Notstromakkus sind alle 4 Jahre auszuwechseln Nachtriggern der Antriebe W hrend der ersten 30 Minuten...

Page 23: ...Melders zum ffnen der Rauchabzugsanlage f hrt Die Verlegeart Unterputz stellt keine zugelassene Verlegeart zum Erreichen eines Funktionserhaltes in Anlehnung an die DIN 4102 Teil 12 dar Der Funktions...

Page 24: ...Kabell ngentabelle Option Weiterleitung Wind Regenmeldung Option Weiterleitung RWA Ausl sung Option Weiterleitung Sammelst rung Option BUS 2 x 2 x O 8 mm oder 5 x 1 5 mm 2 E30 s Kabell ngentabelle Au...

Page 25: ...edienstelle gesetzt werden ZU ZU ZU Anzeige AUF Alarmausl sung RWA Ausl sung Motor Endmodul Aktives Endmodul nur im letzten oder einzigen Melder einsetzen Motor Endmodul nur im letzten oder einzigen A...

Page 26: ...Jumper Achtung Jumper J1 muss in der letzten oder einzigen Hauptbedienstelle gesetzt werden ZU ZU ZU Anzeige AUF Alarmausl sung RWA Ausl sung Motor Endmodul Motor Endmodul nur im letzten oder einzige...

Page 27: ...5C38B592E 75 C9 4 D538 9C385 N 45BE 75 F B2581 D5 Netz Netz Netz sicherung 1 A tr ge Motor Rauchmelder Temperatursichering 72 C Modul 1 Modul 3 Modul 2 Motorsicherung 5 A tr ge Betrieb Akku Motor Haup...

Page 28: ...Steuereinheit an eine VELUX Rauchableitung f r Treppenh user CSJ 1210 oder CSJ 1211 angeschlos sen ist wird das Gesamtsystem als eine Maschine betrachtet die erst dann bet tigt werden darf wenn sie na...

Page 29: ......

Page 30: ...30 VELUX...

Page 31: ......

Page 32: ...RADEMARKS USED UNDER LICENCE BY THE VELUX GROUP AT VELUX sterreich GmbH 02245 32 3 50 BE VELUX Belgium 010 42 09 0 CH VELUX Schweiz AG 062 289 44 45 DE VELUX Deutschland GmbH 040 54 70 70 FR VELUX Fra...

Reviews: