background image

TROUBLESHOOTING

I. Alarm/Walk test LED does not light when unit is walk-tested:

a. No power to detector

- Check cable, connection and power source.

b.LED selector not set to "ALARM"
     - Check jumper position.
c. Not walking into detection pattern
     - Check location of zones using pattern locator and re-test.
d. Background temperature equal or close to body temperature

- Reduced range can be expected when background and body temperature come close

          or are equal to each other.
e. Defective unit

- Replace the circuit board.

II. Alarm/Walk test LED lit continuously:

a. The detector is seeing changing levels of infrared energy
     - Clear area of all people and pets.

- If LED remains lit, cover detector with heavy paper and wait 1 to 2 minutes.

 If LED extinguishes, check each detection zone to locate source of energy.

b. Defective unit

- If LED remains lit after detector has been covered with heavy paper, replace circuit

 

      board.

III. Detector randomly alarms:

a. Power source being interrupted
     - Check wiring and connection.
b. Cover not properly secured or excessive mounting surface vibration
     - Make sure that the cover is firmly in position and that the detector is free from
          vibrations.
c. The detector is seeing changing levels of infrared energy
     - Switch all known sources, such as heaters, lights, air conditioning vents, etc.
         See precautions listed in the section "Selecting mounting location".

Summary of Contents for HAA51

Page 1: ...MODEL HAA51 PASSIVE INFRARED INTRUSION DETECTOR PASSIVE INFRAROOD DETECTOR DETECTEUR D INTRUSION PASSIF INFRAROUGE...

Page 2: ...substantial immunity to false alarms The HAA51 also employs a pulse count triggering circuit which provides further improvement in this respect HAA51 can also be selected for single shot triggering H...

Page 3: ...makes the detector go immediately into the alarm condition whenever an intruder moves in or out of the detection zone The detection circuit requires 1 pulse to activate it It is recommended to use sin...

Page 4: ...ed faulty detector Connect a DC voltmeter with minimum input impedance of 20KOhm V with its positive lead to the T P terminal and the negative lead to the 12V DC terminal as shown in the following dia...

Page 5: ...ot or cold moving air will blow directly onto the unit Avoid aiming the detector at heating or air conditioning vents or ducts exterior metal walls exterior windows or curtains covering windows refrig...

Page 6: ...TEST LED INDICATOR INTO THE INDICATOR HOLE AND KEEP THE HINGED LEVER OF THE TAMPER MICRO SWITCH PRESSED WHEN CLIPPING THE FRONT COVER TESTING a Set the LED selector to ALARM for testing purposes and...

Page 7: ...g levels of infrared energy Clear area of all people and pets If LED remains lit cover detector with heavy paper and wait 1 to 2 minutes If LED extinguishes check each detection zone to locate source...

Page 8: ...installation Mounting location Indoors only flat surface or corner mounting Operating voltage 10 5 16V DC Quiescent current 12mA typical Sensor Dual element pyroelectric sensor with day light filter...

Reviews: