-13-
2 Mechanical Installation
2.1 Installation Environmental Requirements
When installing the PLC to the lead rail, please take account of operability, maintainability and
the surrounding environmental resistance.
Item
Specification
Use environment
Non-corrosive and combustible gas, slight conductive dust (dust)
Altitude
≤ 2000m (80kPa)
Pollution class
L2
Anti-interference
Power cord 2kV (IEC 61000-4-4)
Overvoltage
category
Grade I
EMC
Class B, IEC 61131-2
Vibration
IEC 60068-2-6
5Hz ~ 8.4Hz, 3.5mm, 8.4Hz ~ 150Hz, 1g, X/Y/Z triaxial, 10 cycles/axis
direction
Impact resistance
IEC 60068-2-27
150m/s
2
, 11ms, ± X/Y/Z six directions, 3 times/direction, 18 times in total
Overcurrent
protection
1.5A fuse
Storage temperature
and humidity
Storage temperature: -40℃ ~ +70℃
Relative humidity: < 90% RH, no condensation
Transportation
temperature
and
humidity
Storage temperature: -40℃ ~ +70℃
Relative humidity: < 90% RH, no condensation
Operation
temperature
and
humidity
Operation temperature:-20 ℃ ~ + 55 ℃ (horizontal), 20 ℃ ~ + 45 ℃
(non-horizontal)
Relative humidity: < 95% RH, no condensation
Installation location
and restrictions
Installation location: It can be installed in 4 directions. Please refer to "2.2
Installation Location Requirements” for details.
2.2 Installation Location Requirements
This product can be installed in four positions (i.e. installation direction): horizontal, vertical,
and top and bottom of electric cabinet and horizontal direction is recommended. Different
installation positions have different working temperature requirements and limits. For details, please
refer to "2.1 Installation Environment Requirements".
◼
Optimal installation position
The best installation position of this product is horizontal, and heat dissipation is designed by
natural convection. To ensure normal ventilation and heat dissipation, sufficient wiring space, the
Summary of Contents for VH600
Page 20: ...19 DIN DIN snap Screw...