7
3 Product description
VEGATOR 112 •
46106-EN-210714
3 Product description
3.1 Configuration
The scope of delivery encompasses:
•
Controller VEGATOR 112
•
Documentation
– This operating instructions manual
–
Ex-specific "
Safety instructions
" (with Ex version)
– Safety Manual "Functional safety (SIL) acc. to IEC 61508" (with
SIL version)
–
If necessary, further certificates
The type label contains the most important data for identification and
use of the instrument:
•
Instrument type
•
Information about approvals
•
Technical data
•
Serial number of the instrument
•
QR code for device documentation
•
Manufacturer information
Move to " www.vega.com
" and enter in the search field the serial
number of your instrument.
There you can find the following information about the instrument:
•
Order data
•
Documentation
•
Software
Alternatively, you can find all via your smartphone:
•
Scan the QR-code on the type label of the device or
•
Enter serial number manually in the VEGA Tools app (available
free of charge in the respective stores)
3.2 Principle of operation
The VEGATOR 112 is a double-channel cotroller for level detection
with two level switches with NAMUR interface. Simple monitoring and
control functions can be realised via the integrated relays. Typical
applications are monitoring functions such as overfill and dry run
protection. As an alternative to the double-channel level detection, a
two-point control can be activated.
The VEGATOR 112 controller powers connected sensors and simul-
taneously processes their measuring signals.
When the medium reaches the switching point of the sensor, the sen-
sor current changes. This is measured and evaluated by VEGATOR
112. The change causes the output relays to switch according to the
set operating mode.
Scope of delivery
Type label
Documents and software
Application area
Functional principle