6 Setup
VEGATOR 112 •
46106-EN-210714
> 2,2
I/mA
< 1
3
±1
t/s
1
2
3
1,5
±0,5
Fig. 3: Flow chart function test
1 Simulation full alarm
2 Simulation empty alarm
3 Current measurement status
Test process with VEGASWING
Pressing the test button interrupts the circuit to the sensor and
thereby initiates a restart of the sensor. This only simulates a fault
signal. Check whether the fault signal occurs when the test button is
pressed (red LED lights up). If the line monitoring is deactivated, the
red LED does not light up.
After releasing the test button, the sensor is supplied with voltage
again. After that, if the function is correct, the red fault LED must no
longer light up and the relays are energised or de-energised depend-
ing on the state of the sensor.
Information:
This test is accepted as proof test acc. to WHG.
6.3 Function table "Point level"
The following table provides an overview of the switching conditions
depending on the set mode and the level.
Note:
The switching conditions in the tables are only valid if the mode
switch on the sensor is set to "
Max.
".
Sensor
Controller
Level
Sensor cur-
rent
LED yellow
(output)
LED red
(fault)
Relay
> 2.1 mA
ON
Overfill protection, point
level