6 Setup
6.1 General information
The figures in brackets refer to the following illustrations.
With plastic housings, the switching condition of the electronics can
be checked when the housing cover is closed (control lamp). With the
basic setting, products with a density ≥ 0.7 g/cm³ (0.025 lbs/in³) can
be detected. For products with lower density, the switch must be set
to ≥ 0.5 g/cm³ (0.018 lbs/in³).
On the electronics module you will find the following display and
adjustment elements:
•
Signal lamp (1)
•
DIL switch for adjustment of the density range (2)
Mode adjustment (A/B)
On the signal conditioning instrument VEGATOR 121, 122 or 636 Ex,
via the signal conditioning instrument.
The switching condition can be changed with the A/B switch. You can
set the required mode according to the "Function table" (A - max. de-
tection or overfill protection, B - min. detection or dry run protection).
The switching delay can also be modified on the signal conditioning
instrument (VEGATOR 121, 122 or 636 Ex) signal conditioning instru-
ments).
Note:
Always immerse the tuning fork of VEGASWING 63 in a liquid to test
its function. Do not test the function of VEGASWING 63 with your
hand. This can damage the sensor.
6.2 Adjustment elements
1
2
1
2
Fig. 15: Oscillator SWE60Z - two-wire output
1 Control lamp (LED)
2 DIL switch for adjustment of the density range
Function/Configuration