20
6 Setup
VEGASWING 61 • - transistor (NPN/PNP)
29225-EN-161125
6 Setup
6.1 General information
The figures in brackets refer to the following illustrations.
With plastic housings, the switching condition of the electronics can
be checked when the housing cover is closed (control lamp). With the
basic setting, products with a density ≥ 0.7 g/cm³ (0.025 lbs/in³) can
be detected. For products with lower density, the switch must be set
to ≥ 0.5 g/cm³ (0.018 lbs/in³).
On the electronics module you will find the following display and
adjustment elements:
•
Signal lamp (1)
•
DIL switch for mode adjustment - A/B (2)
•
DIL switch for sensitivity adjustment (3)
Note:
Always immerse the tuning fork of VEGASWING 61 in a liquid to test
its function. Do not test the function of VEGASWING 61 with your
hand. This can damage the sensor.
6.2 Adjustment elements
1
2
3
4
1
2
3
Fig. 13: Oscillator SWE60T - Transistor output
1 Control lamp (LED)
2 DIL switch for mode adjustment
3 DIL switch for sensitivity adjustment
Control lamp for indication of the switching status
•
Green = Output closed
•
Red = Output open
•
red (flashing) = failure
With the mode adjustment (A/B) you can change the switching
condition of the relay. You can set the required mode according to the
Function/Configuration
Signal lamp (1)
Mode adjustment (2)