18
5 Connecting to power supply
VEGASWING 61 • - transistor (NPN/PNP)
29225-EN-161125
3
5
1
2
4
SW E60T
10-55V DC
1
PNP
2 3 4
1
NPN
2 3 4
A
B
0,5 g / cm3
0,7 g / cm3
max 400mA
out
1 2 3 4
+
+
+
Fig. 9: Electronics and terminal compartment, single chamber housing
1 Control lamp
2 DIL switch for mode adjustment
3 DIL switch for switching point adaptation
4 Ground terminal
5 Connection terminals
We recommend connecting VEGASWING 61 in such a way that the
switching circuit is open when there is a level signal, line break or
failure (safe state).
The instrument is used to control relays, contactors, magnet valves,
warning lights, horns as well as PLC inputs.
Caution:
There is no reverse polarity protection. Take note of the polarity of the
output lines.
+
-
1 2 3 4
+
-
Fig. 10: NPN action
Electronics and terminal
compartment
Wiring plan